OPERATION
4.On the PANEL CONFIG screen, set the panel’s meter settings:
Default | Range | Meter Setting | Description |
|
|
|
|
3 | 3 | PHASES | Number of phases |
|
|
|
|
42 | BREAKERS | Number of branch circuit | |
| (even numbers) |
| breakers in the panel |
|
|
|
|
100 | RATING | Panel breaker rating (in amps) | |
|
|
| (see Note 1) |
|
|
|
|
STANDARD | STANDARD | PNL LAYOUT | Panel layout |
| COLUMN |
| (see Note 2) |
|
|
|
|
NOTE 1 Setting the panel breaker rating to 0 silences all main panel breaker alarms and zeroes the panel percent current levels.
NOTE 2 Changing panel layout erases all branch circuit breaker configurations.
To reset all values on the screen to defaults, set the RESET value to
YES.
5.Select OK.
6.Repeat Steps 3 to 5 for each panel containing branch circuit breakers to configure.
7.When all panel configuration is complete, select the button repeatedly to reach the main menu.
8.If all configuration is complete, save your changes by pressing the Reset button on the Power Xpert Gateway Card in the X−Slot communication bay. (The card automatically resets after five minutes.) Otherwise, continue to
Breakers" on page 46.
Configuring Panels Containing Subfeed Breakers
To configure panels containing subfeed breakers (up to 12 per panel):
1.If not already obtained, access the System Setup Level 1 password level. See
2.From the main menu, select METER then PANEL.
3.On the PANEL screen, select the panel number (PNL) to configure, and then select CONFIG.