Control Panel Configuration

OPERATION

Control Panel Configuration

NOTE Use this section only if the optional display is installed.

To set up branch circuit monitoring on your product, configure the panels and branch circuit breakers. Configuration requires System Setup Level 1 password access.

Accessing Configuration

To access the configuration options at System Setup Level 1:

1.In the Setup menu, select ENTER PASSWORD.

2.Use the arrow keys to enter the password (default password is L1 for Level 1).

3.Select DONE. The screen displays the setup options.

To change the default password while logged into System Setup Level 1 access:

1.In the Setup menu, select CHANGE ACCESS LEVEL PASSWORD.

2.Use the arrow keys to enter the new password (A–Z, 0–9, –, blank).

3.Select DONE.

Configuring Panels Containing Branch Circuit Breakers

To configure panels containing branch circuit breakers:

1.If not already obtained, access the System Setup Level 1 password level. See the previous section,

2.From the main menu, select METER then PANEL.

3.On the PANEL screen, select the panel number (PNL) to configure, and then select CONFIG.

EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com