Initial Panel and Breaker Configuration (Using the Display)

INSTALLATION

Initial Panel and Breaker Configuration (Using the Display)

NOTE Use this section only if the optional display is installed.

Configure the panel and breaker data. You can use the following abbreviated instructions or follow the more detailed steps in Panel Configuration" on page 43.

1.From the setup screen, enter the Level 1 access password (default password is L1).

2.Select Meters then Panel, highlight the panel to configure, then select Config.

3.Set the Reset value to Yes and select OK to clear any breaker configuration settings for the panel.

4.Configure the following settings to match the physical panel:

Phases (always three−phase)

Breakers (the number of breakers in the panel) Rating (the rating in Amps of the main panel breaker) Panel Layout (panel numbering style)

5.Highlight the panel number and select Schedule.

6.Highlight the breaker to configure and select Config.

7.Configure the following settings to match the physical breaker:

Phases (number of phases for the breaker) Rating (breaker rating in Amps)

Warning (alarm warning level in %) Overload (alarm overload level in %) CT (the CT ratio – specify 71.9)

8.Configure each installed breaker in the panel.

9.If a second panel is installed, repeat the panel and breaker configuration for the second panel.

10.Activate the reset switch on the bottom of the electronics module: hold the switch for 10 seconds or until the display (if installed) turns off, then release the switch.