Section VIII - Power$ync IIOperation

If the network is powered-up, but not running, or if there are only two machines on the network, the following message may be too quick to be seen.

PLEASE WAIT

TRANSFERRING NETWORK DATA TO

ALL ON-LINE COMPRESSORS

Press F2 to edit the networked pressure deadbands:

1>000U 000L 2>000U 000L 3>000U 000L 4>000U 000L 5>000U 000L 6>000U 000L

UP/DOWN DEADBAND, F1 EDIT, ENTER RETURN

When this screen is displayed, the unload and load pressure settings will be flashing for position number one. To edit position number one, press F1. The unload pressure setting will start flashing slowly, indicating that this number is ready to edit. Use the UP and DOWN arrow keys to change the setting. Once the correct setting has been specified, press ENTER to accept. The load pressure setting will now begin to flash slowly. Follow the same procedure to change the load pressure setting. When the unload and load pressure settings have been accepted, the control will flash both settings, indicating that you can now move to another position setting. To move to the second position, use the UP arrow key. Following the same procedure, adjust the unload and load pressures for all machines on the network. Press ENTER to transfer this data to all on-line compressors and return to Network Configuration Menu 3.

Press the UP arrow key to move to Network Configuration Menu 4. From this display, sequences and schedules can be cleared from all on-line networked compressors at one time, from one machine.

NETWORK CONFIGURATION MENU 4

CLEAR SEQUENCE PRESS F1

CLEAR SEQUENCE AND SCHEDULE PRESS F2 UP FOR NEXT MENU/DOWN FOR PREVIOUS MENU

To clear a particular sequence from the memory, press F1.

When F1 is pressed, the following display will appear:

NETWORK SEQUENCE ERASE

SEQUENCE NUMBER TO CLEAR 1

PRESS ENTER TO ACCEPT VALUE

Use the UP or DOWN arrow keys to scroll to the proper sequence number to clear. Once the proper sequence number is displayed, press ENTER.

The control will display a warning message to prevent the accidental erasure of a particular sequence. This warning message gives the option of continuing the process of erasing a sequence or aborting the process.

NOTICE

YOU HAVE SELECTED SEQUENCE 1 TO CLEAR

NOTICE

PRESS F1 TO CLEAR OR ENTER TO ABORT

Press either F1 or ENTER to complete the process and return the display to Network Configuration Menu 4.

To clear all sequence and schedule information from all compressors on the network, press F2.

NOTICE

YOU WILL CLEAR ALL SEQUENCE AND SCHEDULE

NOTICE

PRESS F1 TO CLEAR OR ENTER TO ABORT

Press either key to complete the process and return to Network Configuration Menu 4.

From Network Configuration Menu 4, press the UP arrow key to move to Network Configuration Menu 5.

NETWORK CONFIGURATION MENU 5

POINTER PASSING DELAY TIME (SECONDS) ___

ENTER ACCEPTS VALUE / EXITS MENU

Press the UP or DOWN key to increase or decrease this value. Press ENTER to return to the previous display.

50

Quincy Compressor® - QSD™

 

 

Page 52
Image 52
Quinny 65040-AB manual To clear a particular sequence from the memory, press F1