Section VIII - Power$ync II™ Operation
Power$ync II™ uses military time (i.e., 8:00AM is 08:00 and 2:00PM is 14:00).
TIME MENU |
|
TO VIEW CURRENT TIME | ➔ PRESS F1 |
TO SET TIME AND DATE | ➔ PRESS F2 |
PRESS ENTER TO RETURN
To view the current time and date without changing them, press F1.
TIME AND DATE MENU |
|
CURRENT TIME ON THIS CONTROL | 00:00 |
CURRENT DATE ON THIS CONTROL | 00/00/00 |
PRESS ENTER TO RETURN |
|
|
|
Press ENTER to return the display to the Time Menu.
To reset the time and date, press F2 at the Time Menu. Because changing the time or date can disrupt schedule information, the control will display the following warning:
NOTICE
YOU ARE ABOUT TO RESET THE CLOCK
TO CHANGE THE TIME AND DATE ➔ PRESS F3
TO ABORT PRESS ENTER
Press F3 to move the display to the Set Time Menu.
SET TIME MENU
CURRENT TIME ➔ 00:00
PRESS ENTER TO ACCEPT VALUE
When this menu is displayed, the hours number will be flashing. Use the UP or DOWN arrow key to change the hour setting. When the hour setting is correct, press ENTER, the minute setting will now be flashing. Follow the above procedure to change the minute setting and press ENTER to accept the change. The control will briefly display a message that it is transferring the new time setting to all
The control will now move to the Set Date Menu.
SET DATE MENU
CURRENT DATE ➔ 00/00/00
PRESS ENTER TO ACCEPT VALUE
Follow the same procedure used to change the time. When the correct date has been entered or confirmed, the display will ask for the day of the week.
SET DAY MENU
CURRENT DAY ➔ MONDAY
PRESS ENTER TO ACCEPT VALUE
The current setting for the day of the week will be flashing. If it is incorrect, use the UP or DOWN arrow key until the correct day of the week is shown. Then press ENTER to accept. The display will indicate that the control is transferring the updated date and day information to the other compressors on the network.
From Compressor Maintenance Menu 1, press the UP arrow key to move the display to Compressor Maintenance Menu 2. This menu allows the operator to test the lift valve system or to check various control settings.
COMPRESSOR MAINTENANCE MENU 2
COMPRESSOR CONTROL TEST | ➔ PRESS F1 |
COMPRESSOR INFORMATION | ➔ PRESS F2 |
UP FOR NEXT MENU/DOWN FOR PREVIOUS MENU
To test the operation of the Power$ync II® valves, press F1. To move to another maintenance menu, use the UP or DOWN arrow keys.
Quincy Compressor® - QSD™ | 53 |
|
|