Section VIII - Power$ync II™ Operation
The Power$ync II™ controller also performs continuing checks on itself while the compressor is in operation. If it detects a fault, it will display one of the following two messages:
NOTICE!
COMPRESSOR HAS SHUT DOWN
**NOTICE** COMMUNICATION FAILURE
REFER TO YOUR SERVICE MANUAL
The Power$ync II™ controller continually checks its communication pathways between boards, even when no pertinent information is being passed. This is done to confirm that all communication pathways are functioning and ready to accept and process signals. If the controller fails to receive the proper response to its attempt to confirm that the communication pathways are functioning properly, it will try two more times and then shut the compressor down. Call your local service representative to correct this problem. The compressor can be operated in
PKG. DISCH TEMP_______
COMPRESSOR HAS SHUT DOWN
**NOTICE** HIGH DISCHARGE TEMPERATURE
TAKE CORRECTIVE ACTION
This display indicates that the controller has detected a high temperature condition at the temperature probe installed in the discharge line from the package to the plant air. This could be the result of a mechanical failure or it could be the result of low coolant flow. This is a serious condition. Do not attempt to restart the compressor until the cause of the shutdown has been determined and corrected. The compressor will not restart as long as the high temperature condition exists. Call your service representative if you cannot determine and correct the cause of the shutdown.
Power$ync II™ is connected to and monitors the state of the motor starter and overload. Should the controller detect a fault condition or detect that a component is not responding to commands, it will illuminate the appropriate LED on the schematic and display one of the following messages:
2 INLET TEMP ______
COMPRESSOR HAS SHUT DOWN NOTICE! HIGH STAGE 2 INLET TEMP TAKE CORRECTIVE ACTION
2 DISCH TEMP ______
COMPRESSOR HAS SHUT DOWN
NOTICE! HIGH STAGE 2 DISCH TEMP
TAKE CORRECTIVE ACTION
1 DISCH TEMP ______
COMPRESSOR HAS SHUT DOWN
NOTICE! HIGH STAGE 1 DISCH TEMP
TAKE CORRECTIVE ACTION
High temperature shutdowns could be caused by high ambient temperatures. Verify that the ambient temperature is within the operating limits of the compressor. A failed or broken vent fan could also cause high temperatures. For
FLUID PRESSURE ______
COMPRESSOR HAS SHUT DOWN
NOTICE! LOW FLUID PRESSURE
TAKE CORRECTIVE ACTION
Low fluid pressure may be caused by a failed fluid pump or regulating valve.
Quincy Compressor® - QSD™ | 63 |
|
|