Section II - Description

Safety Sensors

Four (4) high air temperature RTD’s are standard on QSDunits. These protect the unit by sensing unusually high temperatures and shutting the unit down. Power$ync IImonitors the following areas for high air temperature conditions:

Stage One Discharge

Stage Two Discharge

Stage Two Inlet

Package Discharge

Shutdowns for the Power$ync IIRTD’s is 435°F on discharge locations, and 150°F on Stage 2 inlet and 165°F on package discharge.

In Back-up Mode, two HAT switches monitor stage one and stage two discharge temperature. These switches are nonadjustable and set to trip at approximately 470°F.

NOTE

The back-up control circuit has two (2) HAT switches. There are no indicator lights for these HAT shutdowns. These HAT switches can also cause a shutdown in Power$ync IIMode as a back-up to the RTD’s.

!WARNING

Never remove, bypass or tamper with any safety HAT switch or sensor. Failure to provide this safety feature could cause death, serious injury and property damage. If the compressor is shutting down due to high discharge temperature, contact a qualified service technician immediately.

Indicators

Main Power on Light

Indicates when power from the main disconnect switch has been turned on and there is live power at the compressor starter and control panel. This light will remain on as long as there is power to the unit, regardless of the position of the control selector switch.

!CAUTION

Always check power supply disconnect. The power on light may be inoperable.

High Discharge Air Temperature Lights

Indicates when the unit has sensed an unusually high discharge temperature.

NOTE

There is no indication of high temperature shutdown on the control panel in Back-up Mode.

Motor Overload Fault

Indicates excessive amp draw of drive motor.

NOTE

There is no indication of motor overload shutdown on the control panel in Back-up Mode.

There is a mechanical indicator on the overload relay.

14

Quincy Compressor® - QSD™

 

 

Page 16
Image 16
Quinny 65040-AB manual Indicators, Safety Sensors, Main Power on Light, High Discharge Air Temperature Lights