Section VIII - Power$ync IIOperation

compressor, make sure the load time seconds never go below 15 and unload time seconds are always more than 2. This can be accomplished by sizing air storage correctly for your system demand needs. Use the UP arrow key to move to the next display. Press ENTER to return to Compressor Maintenance Menu 2.

P CALIBRATION DATE:

09/27/00

T CALIBRATION DATE:

09/27/00

UNIT CONFIGURATION DATE:

09/27/00

CURRENT TIME/DATE 00:00

09/27/00

 

 

The P CALIBRATION DATE is the date that the pressure transducers were calibrated. The T CALIBRATION DATE is the date that the temperature sensors were calibrated. These dates should be within one or two months of the unit configuration date. If not, it is possible that the sensors have been recalibrated since the machine left the factory, which may affect the safe operation and warranty of the compressor. Contact your local Quincy service representative to assure that the compressor is operating properly. Use the UP arrow key to move to the next display. Press ENTER to return to Compressor Maintenance Menu 2.

From Compressor Maintenance Menu 2 press the UP arrow key to access Compressor Maintenance Menu 3. This menu allows the user to set the modem baud rate, if the Modem Communications Package has been installed.

COMPRESSOR MAINTENANCE MENU 3 SET MODEM BAUD RATE PRESS F1 COMPRESSOR DIAGNOSTIC MENU PRESS F2 UP FOR NEXT MENU/DOWN FOR PREVIOUS MENU

Press F1 to set the modem baud rate.

Changes to the modem baud rate setting should only be made if the standard modem that is part of the Modem Communications Package option is being replaced with a different model. The correct baud rate for the factory modem is 2400. Changing the baud rate from the factory setting may adversely affect communications.

MODEM BAUD RATE SETUP

SET BAUD RATE _______

PRESS ENTER TO RETURN

Use the UP or DOWN arrow keys to adjust the baud rate to the desired specification. 2400 Baud is the recommended setting. Press ENTER to accept and return to Compressor Maintenance Menu 3.

Press F2 at Compressor Maintenance Menu 3 to view the Compressor Diagnostic Menu:

COMPRESSOR DIAGNOSTIC MENU

VIEW SHUTDOWN LOG

PRESS F1

NETWORK DIAGNOSTIC

PRESS F2

TRANSDUCER PARAMETER CHECK PRESS F3

Press F1 to view the shutdown log.

ENTRY: 01 TIME: 20:16 DATE: 09/27/00

SHUTDOWN CODE: CONTACTOR FAULTY

USE UP/DOWN KEYS TO VIEW OTHER ENTRIES

PRESS ENTER TO RETURN

This display shows shutdown and service alarms beginning with the most recent event. It indicates the entry number, time of the entry, date of the entry and nature of the shutdown or service alarm. Use the UP or DOWN arrow keys to view other entries. The log will hold the 16 most recent alarm conditions. As new alarm conditions occur, the computer will drop the oldest and add the newest. A new machine may have entries in the log resulting from the assembly testing stages.

Quincy Compressor® - QSD™

55

 

 

Page 57
Image 57
Quinny 65040-AB Calibration Date, Unit Configuration Date, Current TIME/DATE, Modem Baud Rate Setup, Network Diagnostic