Feedback Potentiometer wiring in Analog Mode

Closed Loop Position Mode

2k - 10k

2k - 10k

Feedback 1

Feedback 2

14 +5V

5 Ground

11 Ana1

10 Ana2

12 Ana3*

8 Ana4*

FIGURE 58. Pot wiring for RS232 or RC Command and Analog Feedback

Feedback Potentiometer wiring in Analog Mode

When the controller is configured in Analog mode, the analog inputs 1 and 2 are used for commands while the analog inputs 3 and 4 are used for feedback. Analog inputs 3 and 4 have different characteristics than inputs 1 and 2, and so require a lower resistance poten- tiometer in order to guarantee accuracy

Note that the analog inputs 3 and 4 are only available on the AX3500 with PCB revision 3.0 or above. The revision number is marked on the PCB. Roborun will detect the new hard- ware revision and display Rev B on the screen.

2k

2k

2k - 10k

2k - 10k

Command 1

Command 2

Feedback 1

Feedback 2

14 +5V

5 Ground

11 Ana1

10 Ana2

12 Ana3*

8 Ana4*

FIGURE 59. Pot wiring for Analog Command and Analog Feedback

Analog inputs 3 and 4 have different characteristics than inputs 1 and 2, and so require a lower resistance potentiometer in order to guarantee accuracy.

Important Notice

This wiring is also the one to use when the controller is in Analog mode but switched to RS232 after reset using the method discussed in “Entering RS232 from R/C or Analog mode” on page 140

92

AX3500 Motor Controller User’s Manual

Version 1.9b. June 1, 2007

Page 92
Image 92
RoboteQ AX3500 user manual Feedback Potentiometer wiring in Analog Mode, Important Notice, Closed Loop Position Mode