Sierra Raven EDGE manual Configuring the Raven at Polling Host for Modbus on

Models: Raven EDGE

1 141
Download 141 pages 46.3 Kb
Page 65
Image 65

Configuring Modbus/BSAP

The remote Raven then disassembles the packet before trans‐ mitting the RTU ID and serial data to the remote unit. The remote units operate in normal UDP mode and their data is sent to the host via the remote Raven and host Raven.

Configuring the Raven at the

Polling Host for Modbus on

UDP

This section covers a Polling Host with standard Modbus, variations may need additional AT commands.

1. Configure the listening/device ports

In AceManager, select Misc in the side menu.

Figure 8-1: AceManager: Misc

The destination port for the modem at the host needs to match the device port (*DPORT) in use on all the modems at the remote sites. For example, if the remote modem’s device port (*DPORT) is “12345”, then the Modbus host modemʹs S53 destination port should be set to “12345”.

Take note of (or set) the Device Port setting in *DPORT to configure the destination port on the remote modems.

 

 

 

 

 

 

 

Rev 3.0B Feb.08

 

 

 

 

 

61

 

 

 

Page 65
Image 65
Sierra Raven EDGE manual Configuring the Raven at Polling Host for Modbus on, Configure the listening/device ports