4

ConfiguringGenius Blocks

To configure individual features of a Genius block, the block must be the ªactiveº device.

Selecting the Active Device

1.From the Analyze menu, select F3 (Block/Bus Status).

2.Press F1 (Next) or F2 (Previous), to reach the device's description screen.

3.When the desired device appears, press F3 (Ac- tive) to make it the active device. (On a dual bus, the HHM must be on the same bus as the active block. If it is not, either move the HHM or force the bus selection as described on page 5-3).

4.Press D MENU twice to return to the Main Menu.

Configuring Block Features

Select F3 (Configuration), then F2 (Config Block). For Genius blocks, the HHM shows the first configuration display. For example:

P U L S E T E S T

OI

R E F S (blockreferences)

E N A B L E D

 

 

t g l

e n t r

n x t

 

 

 

The HHM shows the feature to be configured (in the example above, it is the Pulse Test option). It also shows the current status of that feature.

When the Hand-held Monitor is set up for a PLC host, line 2 shows the references assigned to the device being configured. If there are ? symbols on the screen, the device's reference address has not yet been configured. If there are * symbols on the screen, a reference address was previously assigned, but it is out of range for the host CPU currently set up for the Hand-held Monitor. If this happens, check the host CPU setup in the HHM Utilities.

When the HHM is set up for a PCIM/QBIM/GENI host, line 2 shows the device type and Device Number (serial bus address) instead.

Because there are so many different device configuration screens, it is not possible to show

them all here. You should refer to the User's Manual for the device you are configuring for descriptions of its configuration screens and detailed instructions for completing them.

Configuration Instructions

1.To advance through the HHM configuration displays making changes as needed, use the F4 (Nxt)key. You can pass through feature dis- plays without making entries.

2.To change a feature, use the TGL and CHNG keys to select choices or enter other values. On screens used to enter individual I/O circuit op- tions, use the F1 ( > ) key to choose a circuit, then select the option using the TGL or CHNG key. On some displays, you can enter new val- ues from the keypad.

3.Press the F3 (Enter) key to save each change.

Copying a Configuration

If there are similar devices on an operating bus, you can use the Copy Configuration feature to copy the configuration from one to the another. Both of the devices must have a Device Number already configured, and they must be operating at the same baud rate. The device to be copied TO must not be Configuration Protected.

The device to be copied FROM must be the active device (move the HHM to that block or select it from the Block/Bus Status screen).

1.To begin, press F3 (Copy Configuration) from the Configuration menu. The HHM shows:

C O P Y C O

N

F I G

F R O M :

n

T O :

c h n g

 

e n t r

 

 

 

2.The Device Number of the active device ap- pears next to the word FROM. Enter the De- vice Number of the device being copied TO. Press F3 (Enter).

3.Press the F4 (Execute) key. The configuration is copied.

4-6

Hand-held Monitor User's Guide ± June 1994

GFK-0121E

Page 33
Image 33