Displaying Field Control Faults
A
1.From the HHM Main Menu, display the Field Control main menu (instructions are on the previous page).
F 1 : M o n i t o r
F 2 : C o n f i g u r a t i o n
2.From this menu, select F1 (Monitor). The fol- lowing menu appears:
F 1 : M o n i t o r I / O
F 2 : F a u l t s
F 3 : P r e v i o u s M e n u
3.Select F2 (faults) to display fault information for the Field Processor and its modules.
The Faults menu appears:
F 1 | F i r s t 1 6 F l t s |
F 2 | L a s t 1 6 F l t s |
F 3 | P r e v i o u s M e n u |
|
|
4.Press F1 to display the first set of 16 faults (one fault at a time). For example:
S l o t | # 1 | F a u l t # 1 |
E X T R A I / O M O D U L E |
< | > | e x i t |
|
|
|
A.Use F1 and F2 to display another fault
B.If there are no faults, the HHM displays the message: NoFaults on the top line.
5.To display the last 16 faults (if any):
A.Press F4 (exit) to return to the screen shown at the top if this page.
B.Press F2 (last 16 faults).
Clearing Field Control Faults
If faults are present, pressing the HHM Clear key here has no effect. To clear faults from the
1.Return to the HHM Main Menu.
2.Press F2 (Analyze).
3.Press F3 (Block./Bus Status).
4.Make the BIU or Field Processor the active de- vice if it is not.
5.Press the Clear key.
Clearing faults from the