Configuring Field Control Station

1.From the HHM Main Menu, display the special set of menus for Field Control.

A.If the Bus Interface Unit or Field Processor is the current-selected device, press F2 (ana- lyze) twice or F3 then F2.

B.If it is NOT the currently-selected device:

H Select F2 (analyze) then F3 (Block/Bus Status).

H Press the F1 (nxt) or F2 (prev) key repeat- edly to reach the serial bus address of the

BIU or Field Processor. Press F3 to make it the active device. Then, press ΔMenu, fol- lowed by F2 (Monitor/Control Ref).

F 1 : M o n i t o r

F 2 : C o n f i g u r a t i o n

From this menu, press F2 (Configuration). This menu appears:

F 1 : G E N I U S

C O N F I G

F 2 : M o d u l e

C o n f i g

F 3 : P r e v i o u s M e n u

HPress F1 to configure the BIU/Field Processor.

HPress F2 to configure individual modules.

Change the Bus Address

When you press F1 (Genius Configuration) from the Configuration menu, the HHM shows the serial bus address previously configured for the BIU or Field Processor:

D e v i c e

S B A

1 4

 

P r v >

e n t r

 

 

If the bus address is correct, press F2 to go on.

Note: If a BIU or Field Processor has a Serial Bus Address conflict on an operating bus, it will not scan the modules in the station until the fault is cleared.

1.If you want to change the address, enter the new address using the keypad.

2.Press F4 (entr). An error message appears if the number has been used for another device.

Select a PLC Reference Address

If the host is not a Series Six PLC or Series Five PLC, no entry is necessary here.

If the host is a Series Six PLC or Series Five PLC, assign an I/O or register reference address.

S t a t T b l A d d r

O O O O O

 

<

>

I O 6 e n t r

shows reference type

1.Use the F3 key to toggle the selection of Series SixI/Omemory, Series Five I/O memory, or register memory. (See the BIU/Field Processor User's Manual for information about memory usage in the Series Five and Series Six PLC).

If I/O memory is used, the amount required is equal to the number of bits of discrete data PLUS analog data. Each analog reference used consumes 16 points.

If register memory is used, an amount is re- quired that is equal to the total number of bytes of input data PLUS all of the output data

2.Key in the number of the block's beginning I/O or register reference. This may be:

SeriesSixI/O

1 to 993

Series FiveI/O

1 to 2041

Registers

1 to 16383

3. Press the F4 (Entr) key.

Configure Additional Features

On the screens that follow, select these features:

HFault Reporting

HGenius bus redundancy

HBSM Controller

HOutput default time (for redundancy)

HCPU redundancy

HDuplex redundancy: default mode for outputs

HConfiguration protection

GFK-0121E

Chapter 4 Device Configuration: Overview

4-7

Page 34
Image 34
Socket Mobile GFK0121E manual Change the Bus Address, Select a PLC Reference Address, Configure Additional Features