Model 9200 Programmable Dual-loop Controller
Electrical Installation
The Model 9200 requires 24VDC, 4 Watt, 60 Hz,
SSi requirement:
MOV’s must be wired across the isolation relay coil terminals on all isolation relays that are connected to solenoids. Further…. MOV’s must be connected across the HOT and NEUTRAL wires when the solenoid is
wired to them. IT IS AN ABSOLUTE MUST to have the MOV’s at BOTH LOCATIONS.
Instrument
On
Flash Card & Flash Card Reader
!Never remove the flash card when the Operator Interface is “ON”.
To properly shut down the Operator Interface, press the “Menu” button, and select “Shutdown”. At the prompt, press “yes” to shut down the operator interface. This will bring you to a conventional Microsoft Windows screen. Sliding the black switch to the “OFF” position (located directly over the green power connector, on the back of the Operator Interface) will turn off the power to the operator interface.
Once the Operator Interface is turned off, remove the compact flash card cover at the top of the display unit, exposing the card. Press the black release button and the card will pop out of the slot. To replace the flash card simply return the card to the slot, making sure that the release button is in it’s “UP” position, and replace the flash card cover to it’s proper position. To restore power to the unit, move the black switch to the right or “ON” position.
Operator Interface Screen Saver
The operator interface has a default screen saver. It automatically “blanks” the screen after ten (10) minutes of
SSi Manual SERIES 9200 | 8 | Programmable |