Model 9200 Programmable Dual-loop Controller

Input Setup

Pressing the “Enter” key takes you to a two-zone screen with the top zone showing the three “inputs”. Pressing the blue “UP” and “DOWN” keys highlights one of the inputs. Pressing the “Enter” key takes you to a menu of parameters that can be assigned to any of the three inputs. Included are thermocouples, voltage, and current inputs.

The lower zone of the “Input Setup” screen contains a table

Parameter

Value

TC Type

S

Filter Time

0

Initial Scale

0

Full Scale

3000

Decimal Point Location

0

Open TC

Up scale

Input offset

0

Use curve

0

Selecting the input type of Inputs 1 through 3 automatically places that parameter in the first table cell (TC Type). Using the blue “UP” and “DOWN” keys to highlight the table cell below the parameter TC Type, and pressing the “Enter” key brings up a numeric keypad that allows you to type in the parameter that is appropriate. If no parameter is necessary simply move the highlight down to the next parameter and enter that if required. Continue until all values associated/required by the input type have been entered. Pressing the “Esc” key takes you back to the configuration menu.

NOTE: See the following list of “Input Selections”

Input type selections for the Series 9200 -

Input Type Options

T/C’s B, C, E, J, K, N, NNM, R, S, T

 

781.25, 195.3125, 25, 12.5mV’s and 2.5 and

 

1.25 Volts

 

 

 

78.125, 19.53125 Millivolts

4 – 20 mA (124 Ohm precision shunt required)

25 Volts (Requires internal jumper)

12.5Volts (Requires internal jumper)

781.25Millivolts (Requires internal jumper) 195.3125 Millivolts (Requires internal jumper)