Model 9200 Programmable Dual-loop Controller

Output Setup

Pressing the “Enter” key takes you to a page similar to the one input setup with the exception that these are outputs, not inputs.

Pressing the “Enter” key when Output 1 is highlighted displays a screen with many parameters listed that could be assigned to Output 1. Remember that this is NOT control output, but an auxiliary output. For example you can re-transmit PV1 ( Process Variable 1 - %C) to a chart recorder or an analog input board in a PLC. Pressing the “Enter” button assigns whichever parameter you have highlighted as the “value” for the assignment parameter.

The blue “UP” and “DOWN” arrow keys highlight either Output 1 or Output 2. Pressing the “Enter” key takes you to a List of of outputs. Selecting an output returns a screen similar to the one below.

Parameter

Value

Assignment

 

Offset

 

Range

 

Pressing the “Esc” key returns you to the configuration menu.

Passcode and Alarm

Highlighting “Passcode and NC/NO” and pressing the “Enter” key takes you to the following screen:

Parameter

Value

Level 1 Code

1

Level 2 Code

2

Web Level 1 Code

111

Web Level 2 Code

222

No Alarm

Contact is Open (NO)

Web Change Enable

1

Alarm Text Setup

 

Alarm 0

User Alarm 0

………

………..

Alarm 99

User Alarm 99

The values shown in the above table are the default values. The parameter “No Alarm” means that if there is NO CONTROLLER ALARM, the controller alarm relay is NO. Scroll down until “NO ALARM” is highlighted. Press “Enter”. On the numeric keypad use a “1” and press the “Enter” key to change the state of the relay to “Contact is Closed”, and use a “0” and press the “Enter” key to change the state of the relay to “Contact is Open”. This allows the operator to assign the controller alarm as a NC contact such as a 1400° F alarm.

When highlighting a parameter and pressing the “Enter” key a numeric keypad is displayed allowing you to enter your value. Enter that value using the touch-screen keypad and press the “Enter” key. The change will be made. Press the “Esc” key to return to the configuration menu.

Alarm 0 through 99

SSi Manual SERIES 9200

39