Installing Your S100

Install the S100 in a physically secure location with strong physical access controls.

Symmetricom recommends that you read the operating environment requirements and other specifications in “S100 Specifications” on page 119, before starting.

WARNING!

To prevent electrical shock or injury, DO NOT remove the S100 cover.

Dangerous voltages exist within this enclosure!

Rack Mounting

The S100 is designed for mounting in a standard 19-inch (48.26 cm) rack. It is important to keep the fan inlet and outlet areas clear to maintain air flow. If the unit is installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may become greater than that of the room. Be sure that the ambient temperature is no higher than 50°C/122°F. Make sure the unit is properly balanced and grounded.

Primary Power Connection

The S100 uses external AC power.

The unit has a power cable with a PH-386, IEC 320-C-13 three-conductor female connector on the computer end of the cable. The other end of the cable has a NEMA 6-15P grounding plug (US Standard, 15-amp, 125-volt, straight-blade plug).

Important Safety Instructions!

When using your telephone equipment, basic safety precautions should always be followed to reduce the risk of fire, electric shock and injury to persons. Do not use this product near water or in a damp location.

Caution: To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord.

S100 User Guide – Rev. D – June 2005

19