E6581741

EtherNet/IP parameters

 

 

 

Title

Communi

 

Function

Description

Factory

cation No.

 

setting

 

 

 

 

 

 

 

 

Monitor of the EtherNet error.

-

 

 

 

 

0: No error/clear error

 

c536

C536

 

EtherNet Error

1: Modbus TCP IO Scanning timeout

 

 

 

 

 

2: Network overload

 

 

 

 

 

3: Loss of Ethernet carrier

 

 

 

 

 

Enables web server.

1

c554

C554

 

Web service (*3)

0: Disable

 

 

 

 

 

1: Enable

 

 

 

 

 

Monitor the inverter status.

-

c555

C555

 

Drive Status

3: Gate Block

 

 

4: Run

 

 

 

 

 

 

 

 

 

 

23: Fault

 

Modbus TCP parameters

 

 

 

Title

Communi

 

Function

Description

Factory

cation No.

 

setting

 

 

 

 

c600-

C600-

 

IP Master (*3)

The IP address for PLC(Master) of the Modbus TCP.

0.0.0.0

c603

C603

 

 

 

 

 

 

 

 

 

Enables IO Scan function.

0

c604

C604

 

IO Scan active (*3)

0: Non-active

 

 

 

 

 

1: Active

 

(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.

Mandatory

action

Warning

Set up “Communication error trip function (c100 to c103 and c523)” to stop the inverter when EtherNet/IP™ - Modbus® TCP communication is deactivated.

When the parameters are changed, please reset (power supply reset or f899=1) the inverter for the changes to take effect.

- 10 -

Page 11
Image 11
Toshiba IPE002Z instruction manual Monitor of the EtherNet error No error/clear error C536