E6581741

3.2.4.7. fd01 (Inverter operating status 1)

bit

Function

0

1

Note

0

Failure FL

No output

Under in

-

progress

 

 

 

Trip status includes rtry and

 

 

 

 

1

Failure

Not tripped

Tripped

the trip retention status are also

 

 

 

 

regarded as tripped statuses.

2

Alarm

No alarm

Alarm issued

-

3

Under voltage (moff)

Normal

Under voltage

-

 

 

 

 

THR1: pt = setting value, vl,

4

Motor selection (1 or 2)

Motor 1 (THR1)

Motor 2 (THR2)

vlv, vb, thr

(THR 2 selection)

THR2: pt = 0, f170, f171,

 

 

PID control

PID control

f172, f173

5

PID control off

-

permitted

prohibits

 

 

 

 

Acceleration/deceleratio

Acceleration/dec

Acceleration/dec

AD1: acc, dec

6

n pattern selection (1 or

eleration pattern

eleration pattern

AD2: f500, f501

 

2)

1 (AD1)

2 (AD2)

 

7

DC braking

OFF

Forced DC

-

braking

 

 

 

 

8

Jog run

OFF

Jog run

-

9

Forward / reverse run

Forward run

Reverse run

-

10

Run/stop

Stop

Run

-

11

Coast stop (ST = OFF)

ST=ON

ST=OFF

-

12

Emergency stop

No emergency

Emergency

-

stop status

stop status

 

 

Standby: Initialization

 

 

 

 

 

 

 

 

completed, not failure stop

13

Standby ST=ON

Start-up process

Standby

status, not alarm stop status

 

 

 

 

(moff, ll forced stop),

 

 

 

 

ST=ON, and RUN=ON

 

 

 

 

Standby: Initialization completed,

14

Standby

Start-up process

Standby

not failure stop status and not

alarm stop status (moff, ll

 

 

 

 

 

 

 

 

forced stop)

15

(Reserved)

Undefined

-

Note: Don’t use the reserved bit for the judgment.

3.2.4.8. fd00 (Output frequency)

The current output frequency is read into 0.01Hz of units and by the hexadecimal number. For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.

Since the minimum unit is 0.01%,

0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)

 

Also about the following parameters, these are the same as this.

 

- fd22 (Feedback value of PID)

Unit: 0.01Hz

- fd16 (Estimated speed)

Unit: 0.01Hz

- fd29 (Input power)

Unit: 0.01kW

- fd30 (Output power)

Unit: 0.01kW

- 18 -