3.2.4.Command data (c001-c006), Monitor data (c021-c026)

The outline is indicated about the setting item c021 – c026 in Instance 102/152 and communication functional description for details.

of parameter c001 – c006 and 105/155 of use. Please refer to a

3.2.4.1. How to use Instance 102/152 and 105/155

Instance 102/152 and 105/155 choose a command or the monitor of the driving state by a menu of c001

-c006 and c021 - c026 and can perform the communication that is cyclic of EtherNet/IP™ and Modbus® TCP (ID = 255).

Example 1: Command transmitting by output Instance 102

If the command value “c400” set to parameter fa06, Choose parameter fa06 (a communication option command) for command data (c001=1 (fa06)).

For example, please set C400 in FA06 when you want to send the command from an EtherNet/IP™ option and the availability of the frequency order and a driving order. (Please refer to ”3.2.4.2”)

VF-MB1/S15

IPE002Z

 

Parameter

Value

c001

1 (fa06)

c002

...

c003

...

...

...

"0xC400" is set to parameter fa06

EtherNet/IP Master

Output Instance 102

Byte

Value

0

00

1

C4

2

...

3

...

...

...

Example 2: State monitoring by the input instance 152.

When you want to monitor the output current, set “3 (fd03)” to parameter c021.

The value of the parameter fd03 specified as 0 and 1 byte of the input instance 152 with the parameter c021 is inputted.

VF-MB1/S15

 

IPE002Z

 

 

 

 

 

 

 

 

Parameter

Value

 

 

c021

3 (fd03)

 

 

c022

...

 

 

c023

...

 

 

...

...

 

The value of a parameter fd03 (0x1234) is outputted.

EtherNet/IP Master

Input Instance 152

Byte

Value

0

34

1

12

2

...

3

...

...

...

- 14 -