E6581741

3. Parameters

3.1. Communication parameters

Set up the inverter parameters as follows. It is necessary to reset the inverter to update the parameter. This option doesn't operate if these parameters are not correctly set.

Title

Communi

Function

Description

Factory

cation No.

setting

 

 

 

 

 

 

0: Terminal board

 

 

 

 

1: Panel keypad (including remote keypad)

1

cmod

0003

Command mode selection

2: RS485 communication

 

 

 

3: CANopen communication

 

 

 

 

4: Communcation option

 

 

 

 

0: Setting dial 1 (save even if power is off)

 

 

 

 

1: Terminal board VIA

 

 

 

 

2: Terminal board VIB

 

 

 

 

3: Setting dial 2 (press in center to save)

 

 

 

 

4: RS485 communication

 

 

 

Frequency setting mode

5: UP/DOWN from external logic input

0

fmod

0004

6: CANopen communication

selection 1

 

 

7: Communication option

 

 

 

 

 

 

 

 

8: Terminal board VIC

 

 

 

 

9, 10: -

 

 

 

 

11: Pulse train input

 

 

 

 

12, 13: - (*1)

 

 

 

 

14: sr0 (*1)

 

 

 

 

1: 2 poles

 

 

 

 

2: 4 poles

 

 

 

 

3: 6 poles

 

f856

0856

Number of motor pole pair for

4: 8 poles

2

communication

5: 10 poles

 

 

 

 

 

 

6: 12 poles

 

 

 

 

7: 14 poles

 

 

 

 

8: 16 poles

 

f899

0899

Communication function reset

0: -

0

1: Reset (after execution: 0)

 

 

 

 

(*1): There selections are effective in only VF-S15.

 

 

 

 

 

 

 

Title

Communi

Function

Description

Factory

cation No.

setting

 

 

 

 

 

 

0: -

1

 

 

 

1: fa06 (Communication command 1)

 

 

 

 

2: fa23 (Communication command 2)

 

 

 

 

3: fa07 (Frequency command, 0.01Hz)

 

 

 

 

5: fa50 (Terminal output data)

 

c001

C001

Scanner input 1 address (*3)

6: fa51 (FM analog output)

 

8: f601 (Stall prevention level, %)

 

 

 

 

 

 

 

 

13: acc (Acceleration time 1, 0.1s) (*2)

 

 

 

 

14: dec (Deceleration time 1, 0.1s) (*2)

 

 

 

 

15: ul (Upper limit, 0.01Hz)

 

 

 

 

16: vb (Torque boost value 1, 0.1%)

 

 

 

 

17: vlv (Base frequency voltage 1, 0.1V)

 

c002

C002

Scanner input 2 address (*3)

0-17 (Same as c001)

3

c003

C003

Scanner input 3 address (*3)

0-17 (Same as c001)

0

c004

C004

Scanner input 4 address (*3)

0-17 (Same as c001)

0

c005

C005

Scanner input 5 address (*3)

0-17 (Same as c001)

0

c006

C006

Scanner input 6 address (*3)

0-17 (Same as c001)

0

(*2): The unit depends on the f519 setting.

(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.

- 7 -

Page 8
Image 8
Toshiba IPE002Z instruction manual Parameters, Communication parameters