<Example of setting>

The example below shows how to configure the local/remote operation.

F terminal

Operating command

R terminal

EtherNet/IP-Modbus TCP local/remote

 

(Terminal in this example) switching

VIA terminal

Operation frequency command

<Wiring>

Variable resistor for adjustment 10k ohm

Operation command

EtherNet/IP-Modbus TCP

/local Switch

 

VF-MB1

PP

 

VIA

SW1*

 

CC

SOURCE

PLC

 

F

SINK

 

R

 

CC

 

<Parameter setting>

cmod(Command mode selection) = 0 (Terminal board) fmod(Frequency setting mode selection 1) = 1 (VIA)

f112(Input terminal selection 2 (R)) = 48 (Remote/Local control)

<Operation>

R-CC terminal open: VF-MB1 is controlled as a slave device of the EtherNet/IP™ - Modbus® TCP.

R-CC terminal closed:

F-CC terminal short to RUN F-CC terminal open to STOP

Output frequency is set up by the VIA signal input.

(Note)

When the local(HAND) / remote key (f750=2) is chosen as EASY key selection and the EASY key lamp of an inverter front panel is on, priority is most given to operation by a panel. (Refer to the inverter instruction manual for details).