E6581741

Examples of Instance 101/151

Access the inverter parameter is enabled using byte 4 to 6 of this Instance.

Set the communication number of the parameter to byte 4, 5 (Index), and the value to byte 6, 7 (Data).

cRead the parameter cmod (Command mode selection, communication number is 0003).

Instance

Byte

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Hex.

Output Instance 101

5, 4

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

0x0003

7, 6

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

Input Instance 151

5, 4

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

0x0003

(cmod is 0.)

7, 6

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0x0000

dRead the parameter f268 (Initial value of UP/DOWN frequency).

Instance

Byte

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Hex.

Output Instance 101

5, 4

0

0

0

0

0

0

1

0

0

1

1

0

1

0

0

0

0x0268

7, 6

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

Input Instance 151

5, 4

0

0

0

0

0

0

1

0

0

1

1

0

1

0

0

0

0x0268

(f268 is 60.0Hz.)

7, 6

0

0

0

1

0

1

1

1

0

1

1

1

0

0

0

0

0x1770

3Write “60 (Hz)” to the parameter sr1 (Preset speed 1, communication number is 0018).

Instance

Byte

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Hex.

Output Instance 101

5, 4

1

0

0

0

0

0

0

0

0

0

0

1

1

0

0

0

0x8018

7, 6

0

0

0

1

0

1

1

1

0

1

1

1

0

0

0

0

0x1770

 

Input Instance 151 (OK)

5, 4

1

0

0

0

0

0

0

0

0

0

0

1

1

0

0

0

0x8018

7, 6

0

0

0

1

0

1

1

1

0

1

1

1

0

0

0

0

0x1770

 

Input Instance 151 (NG)

5, 4

1

1

0

0

0

0

0

0

0

0

0

1

1

0

0

0

0xC018

(Error code *)

7, 6

0

0

0

1

0

0

0

1

0

0

0

0

0

0

0

0

0x1100

*Data of "Error code"

0x1100: Data out of range

0x1101: Bad address

- 50 -

Page 51
Image 51
Toshiba IPE002Z instruction manual Examples of Instance 101/151, Output Instance 0x0003 Input Instance Cmod is 0x0000