E6581741
3.2.4.13. fc91 (Alarm code)
bit
Function
0
1
Remarks
(Code displayed on
the panel)
0 | Normal | Alarming | c flicking | ||
1 | Inverter over load alarm | Normal | Alarming | l flicking | |
2 | Motor over load alarm | Normal | Alarming | l flicking | |
3 | Over heat alarm | Normal | Alarming | h flicking | |
4 | Over voltage alarm | Normal | Alarming | p flicking | |
5 | Main circuit undervoltage alarm | Normal | Alarming | - | |
6 | main device overheat alarm | Normal | Alarming | l flicking | |
7 | Under current alarm | Normal | Alarming | - | |
8 | Normal | Alarming | - | ||
9 | Braking resistor overload alarm | Normal | Alarming | - | |
10 | Cumulative operation hours alarm | Normal | Alarming | - | |
11 | Option communication alarm | Normal | Alarming | - | |
12 | Serial communication alarm | Normal | Alarming | - | |
13 | MOFFMS (MSrelay off or MOFF) | Normal | Alarming | - | |
14 | Stop after instantaneous power off | - | Dec., Under | Refer to f302 | |
stop | value | ||||
|
|
| |||
15 | Stop after LL continuance time | - | Dec., Under | Refer to f256 | |
stop | value | ||||
|
|
|
3.2.4.14. fd06 (Input TB Status)
bit | TB Name |
|
|
|
|
|
|
| Function (Parameter) |
|
|
|
|
|
| 0 |
| 1 | |||||||||
0 | F |
|
| Input terminal function selection 1 (f111) |
|
|
|
|
|
|
| ||||||||||||||||
1 | R |
|
| Input terminal function selection 2 (f112) |
|
|
|
|
|
|
| ||||||||||||||||
2 | RES |
|
| Input terminal function selection 3 (f113) |
|
|
|
|
|
|
| ||||||||||||||||
3 | S1 |
|
| Input terminal function selection 4 (f114) |
|
|
| OFF |
| ON | |||||||||||||||||
4 | S2 |
|
| Input terminal function selection 5 (f115) |
|
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
| |||||||||||||||||||
5 | S3 |
|
| Input terminal function selection 6 (f116) |
|
|
|
|
|
|
| ||||||||||||||||
6 | VIB*1 |
|
| Input terminal function selection 7 (f117) |
|
|
|
|
|
|
| ||||||||||||||||
7 | VIA*1 |
|
| Input terminal function selection 8 (f118) |
|
|
|
|
|
|
| ||||||||||||||||
5 to 15 | (Reserved) |
|
| - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Undefined | ||
Note: Don't use the reserved bit for the judgment. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
*1: VIA/ VIB are input terminal function when f109 is logic input. |
|
|
|
|
|
|
|
| |||||||||||||||||||
*The input terminal function is selected by each parameter. |
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
Example: Data set for FE06 when the F and RES terminals are ON = 0005H |
|
| |||||||||||||||||||||||||
| BIT15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| BIT0 |
|
| ||||||
| FE06: |
| 0 |
| 0 |
| 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 0 | 0 | 0 | 1 |
| 0 | 1 |
|
|
| ||
|
|
|
|
|
|
| 0 |
|
| 0 |
|
|
|
| 0 |
|
|
| 5 |
|
|
|
|
|
- 20 -