| E6581741 | ||
|
|
|
|
|
|
|
| |
Title | Communi | Function |
|
| Description |
| Factory | |
cation No. |
|
|
| setting | ||||
|
|
|
|
|
| |||
|
|
| 0: | - | (Status information 1) |
| 1 | |
|
|
| 1: fd01 |
|
| |||
|
|
| 2: fd00 | (Output frequency, 0.01Hz) |
|
| ||
|
|
| 3: fd03 | (Output current, 0.01%) |
|
| ||
|
|
| 4: fd05 | (Output voltage, 0.01%) |
|
| ||
|
|
| 5: fc91 | (Alarm information) |
|
| ||
|
|
| 6: fd22 | (PID feedback value, 0.01Hz) |
| |||
|
|
| 7: fd06 | (Input terminal board status) |
| |||
|
|
| 8: fd07 | (Output terminal status) |
|
| ||
|
|
| 9: fe36 | (VIB input, 0.01%) |
|
| ||
|
|
| 10: fe35 | (VIA input, 0.01%) |
|
| ||
|
|
| 11: fe37 | (VIC input, 0.01%) |
|
| ||
|
|
| 12: fd04 | (Input voltage (DC detection), 0.01%) |
| |||
|
|
| 13: fd16 | (Estimated speed 0.01Hz) |
|
| ||
|
|
| 14: fd18 (Torque, 0.01%) |
|
| |||
|
|
| 15: | - |
|
|
| |
|
|
| 16: | - |
|
|
| |
c021 | C021 | Scanner output 1 address (*3) | 17: | - |
|
|
| |
18: | - |
|
|
| ||||
|
|
|
|
|
| |||
|
|
| 19: f880 | (Free notes) |
|
| ||
|
|
| 20: fd29 | (Input power, 0.01kW) |
|
| ||
|
|
| 21: fd30 | (Output power, 0.01kW) |
|
| ||
|
|
| 22: fe14 | (Cumulative operation time, hour) |
| |||
|
|
| 23: fe40 (FM terminal output monitor, 0.01%) |
| ||||
|
|
| 24: | - |
|
|
| |
|
|
| 25: fd20 (Torque current, 0.01%) |
|
| |||
|
|
| 26: fd23 (Motor overload factor, 0.01%) |
| ||||
|
|
| 27: fd24 (Drive overload factor, 0.01%) |
| ||||
|
|
| 28: fd25 (PBR overload factor, %) |
|
| |||
|
|
| 29: fd26 (Motor load factor, %) |
|
| |||
|
|
| 30: fd27 (Drive load factor, %) |
|
| |||
|
|
| 31: fe56 (Pulse train input, pps) |
|
| |||
|
|
| 32: fe70 (Drive rated current, 0.1A) |
|
| |||
|
|
| 33: fe76 (Input | 10f749) |
| |||
|
|
| 34: fe77 (Output | 10f749) |
| |||
|
|
| 35: fd83 (IGBT temperature, degree C) |
| ||||
c022 | C022 | Scanner output 2 address (*3) |
| 2 | ||||
c023 | C023 | Scanner output 3 address (*3) |
| 0 | ||||
c024 | C024 | Scanner output 4 address (*3) |
| 0 | ||||
c025 | C025 | Scanner output 5 address (*3) |
| 0 | ||||
c026 | C026 | Scanner output 6 address (*3) |
| 0 | ||||
|
|
| 16 characters |
|
| |||
c081- | C081- |
| The | device | name is required if the | card uses | 0,0,0,0, | |
c096 | C096 | Device Name | DHCP to obtain its IP Address. |
| 0,0,0,0 | |||
Refer to "3.2.1 Device name | ||||||||
|
|
|
| |||||
|
|
| details. |
|
|
| ||
c100 | C100 | Communication error | 0.0 - 100.0 sec. |
| 0.0 | |||
detection delay time |
| |||||||
|
|
|
|
|
|
| ||
|
|
| 0: Stop and controlled by cmod, fmod |
| ||||
|
|
| 1: Operation continue |
|
| |||
| C101 | Inverter operation at the | 2: Deceleration stop |
| 4 | |||
c101 | 3: Coast stop |
| ||||||
communication loss action |
| |||||||
|
| 4: Network error stop (err8 trip) |
|
| ||||
|
|
|
|
| ||||
|
|
| 5: Preset speed operation (by c102 setting) |
| ||||
|
|
|
|
|
|
| ||
c102 | C102 | Preset speed operation | 0: None |
|
| 0 | ||
selection | 1 to 15: Preset speed |
|
| |||||
|
|
|
| |||||
|
|
| 0: Disconnection detection |
| 0 | |||
|
| Communication | 1: | When communication mode enable (Both |
| |||
c103 | C103 | cmod | and fmod are set CANopen or |
| ||||
condition selection |
| |||||||
|
| communication option) only |
|
| ||||
|
|
|
|
| ||||
|
|
| 2: 1 + Driving operation |
|
|
(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.
(*4): (V[R) does not work for this parameter.
- 8 -