E6581741
Instance Services
Service Code | Service Name | Description of Service |
0x0E | Get_Attribute_Single | Read one attribute |
0x10 | Set_Attribute_Single | Write one attribute |
Attribute ID of all parameters are 3. Moreover, about the instance ID of each parameter, it becomes "parameter communication number + 4000H".
In the case of the parameter from which a communication number begins in "F", it becomes "parameter communication number - 0x8000 (same as bit15 set to 0)".
About the detail contents of a parameter, please refer to a
Example 1:
In case of Basic parameter “cmod - Command mode selection”,
Communication No: 0003 -> Instance ID: 4003
Example 2:
In case of Extended parameter “f268 - Updown frequency default value”,
Communication No: 0268
Example 3:
In case of Monitor parameter “fe03 - Output current”,
Communication No: FE03 -> Instance ID: 7E03
* Monitor parameter can access "Get" only.
For example, when "Acc. time" is set to 5 sec., since the minimum unit is 0.1s, 5 / 0.1 = 50 = 32H
Since the communication number of "Acc. time" is "0009", it writes "32H" in instance ID "4009."
Moreover, when the "highest frequency" is read, "1F40H" is read. 0x1F40 = 8000 (Dec.)
Since the minimum unit is 0.01Hz, 8000 * 0.01 = 80Hz
- 34 -