8-2-4. Automatic Operation

(1)As shown in Fig. 8-2-9, the operation mode (COOL, DRY, HEAT) is selected according to the outside temperature and room temperature when the operation has started.

The operation in Fan mode continues until an operation mode is selected.

If the room temperature is 20°C or higher when “AUTO” operation started within 2 hours after “HEAT” operation had stopped, select an opera- tion mode after Fan operation of ultra low fan.

In AUTO operation, the set temperature of each operation can be corrected by the remote controller in the range of 17 to 30°C.

(2)After selecting the operation mode (COOL, DRY, HEAT), select an operation mode again when a status that the compressor was turned off by the room temperature or outside air temperature continues for 15 minutes.

(3)Powerful Cool mode control

When the outside temperature is above 32°C and indoor temperature is above 28°C, select Cool mode control. In Cool mode, the air flow louver directs downward. When the room tem- perature gains access to the set temperature, it becomes cool memory position.

TA

28

26

24

23

20

Heating with setting on remote controller Ts = 25˚C

Powerful Cooling/Drying with setting on remote controller Ts = 25˚C

Cooling/Drying with setting on remote controller Ts = 25˚C

Monitoring

(Follow to the Fan control in previous mode when being selected again.)

Ts correction by outside temperature (To)

5

15 18

24

32

To

–2

 

–1

 

 

0

 

+1

Fig. 8-2-9

8-3. Temporary Operation

8-3-1. Temporary Auto Operation

Temporary Auto operation, existence of Auto Restart, and Temporary Cooling operation can be set by the TEMPORARY button of the indoor controller.

 

 

 

 

 

 

 

 

 

 

TEMPORARY

 

 

 

 

 

 

 

 

 

 

button

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMPORARY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 8-3-1

 

 

 

 

 

 

 

 

 

 

 

TEMPORARY button

 

 

 

 

 

 

 

 

 

Control

 

 

OFF ON

Temporary Auto operation start

After pushing button

 

Auto Restart control select

for 3 seconds

 

 

 

 

 

 

 

 

 

 

 

After pushing button

 

 

 

 

 

 

 

 

Temporary Cooling

for 10 seconds

 

 

 

 

 

 

 

 

 

operation start

 

 

 

 

 

 

 

 

 

 

 

When the TEMPORARY button is pushed, the Auto operation with set temperature fixed at 25°C starts. Controlling is same as that of Auto opera- tion by the remote controller.

When the TEMPORARY button is pushed again, the operation stops.

During Temporary Auto operation, operation by the remote controller is accepted.

Using the Auto Restart function, the Temporary Auto operation starts when power failure is reset.

8-3-2. Temporary Cooling Operation

When the TEMPORARY operation button keeps pushed for 10 seconds, Cooling operation of which compressor motor speed and the indoor fan speed are fixed starts.

Compressor motor speed : 10 : 30 rps

13 : 30 rps

Indoor fan speed : Low

When the TEMPORARY operation button is pushed again, the operation stops.

Auto Restart function is unavailable.

– 32 –

Page 32
Image 32
Toshiba RAS-13YKV-E Temporary Operation, Automatic Operation, Temporary Auto Operation, Temporary Cooling Operation