1. SPECIFICATIONS

1-1. Specifications

RAS-10YKV-E/RAS-10YAV-E

Unit model

Indoor

 

 

 

RAS-10YKV-E

 

Outdoor

 

 

 

 

RAS-10YAV-E

Current limited

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

 

2,7

Cooling capacity range

 

 

(kW)

 

0,8 – 3,4

Heating capacity

 

 

 

(kW)

 

3,6

Heating capacity range

 

 

(kW)

 

0,8 – 6,2

Power supply

 

 

 

 

220 – 230 –240V – 1Ph – 50/60Hz

Electric

Indoor

Operation mode

 

Cooling

 

Heating

characteristics

 

Running current

(A)

0,15

 

0,15

 

 

Power consumption

(W)

30

 

30

 

 

Power factor

(%)

87

 

87

 

Outdoor

Operation mode

 

Cooling

 

Heating

 

 

Running current

(A)

3,39 / 3,23 / 3,09

 

4,40 / 4,20 / 4,02

 

 

Power consumption

(W)

670

 

870

 

 

Power factor

(%)

90

 

90

 

 

Starting current

(A)

4,55 / 4,35 / 4,17

COP (Cooling/Heating)

 

 

 

 

 

3,86 / 4,00

Operating noise

Indoor

High

(Cooling / Heating)

(dB•A)

 

38 / 39

 

 

Medium

(Cooling / Heating)

(dB•A)

 

34 / 35

 

 

Low

(Cooling / Heating)

(dB•A)

 

30 / 30

 

Outdoor

(Cooling / Heating)

(dB•A)

 

45 / 46

Indoor unit

Unit model

 

 

 

RAS-10YKV-E

 

Dimension

Height

 

(mm)

 

265

 

 

Width

 

(mm)

 

790

 

 

Depth

 

(mm)

 

189

 

Net weight

 

 

(kg)

 

8

 

Fan motor output

 

(W)

 

19

 

Air flow rate

(Cooling / Heating)

(m³/h)

 

480 / 520

Outdoor unit

Unit model

 

 

 

 

RAS-10YAV-E

 

Dimension

Height

 

(mm)

 

550

 

 

Width

 

(mm)

 

780

 

 

Depth

 

(mm)

 

270

 

Net weight

 

 

(kg)

 

38

 

Compressor

Motor output

(W)

 

750

 

 

Type

 

 

Twin rotary type with DC-inverter variable speed control

 

 

Model

 

 

 

DA91A1F-44F

 

Fan motor output

 

(W)

 

40

 

Air flow rate

(Cooling / Heating)

(m³/h)

 

2120 / 2120

Piping connection

Type

 

 

 

Flare connection

 

Indoor unit

Liquid side

 

 

Ø 6,35

 

 

Gas side

 

 

Ø 9,52

 

Outdoor unit

Liquid side

 

 

Ø 6,35

 

 

Gas side

 

 

Ø 9,52

 

Maximum length (Per unit)

(m)

 

15

 

Maximum chargeless length

(m)

 

15

 

Maximum height difference

(m)

 

10

Refrigerant

Name of refrigerant

 

 

 

R410A

 

Weight

 

 

(kg)

 

0,8

Wiring connection

 

Power supply

 

3 Wires : includes earth

 

 

Interconnection

 

4 Wires : includes earth

Usable temperature range

Indoor

(Cooling / Heating)

(°C)

21 – 32 / 0 – 28

 

 

Outdoor (Cooling / Heating)

(°C)

10 – 43 / –10 – 21

Accessory

Indoor unit

Installation plate

 

 

1

 

 

Wireless remote control

 

 

1

 

 

Label

 

 

 

2

 

 

Remote controller holder

 

 

1

 

 

Pan head wood screw

 

 

2 (Ø 3,1 x 16L)

 

 

Purifying filter

 

 

1

 

 

Deodorizing filter

 

 

1

 

 

Batteries

 

 

2

 

 

Mounting screw

 

 

6 (Ø 4 x 25L)

 

 

Installation manual

 

 

1

 

 

Owner's manual

 

 

1

 

Outdoor unit

Drain nipple

 

 

1

• The specifications may be subject to change without notice for purpose of improvement.