10-4-3. Caution at Servicing

10-4-3. Caution at Servicing

(1)After servicing, push the START/STOP button to return to the normal mode.

(2)After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power supply again so that memory in the microcomputer returns the initial status. However, the check codes are not deleted even if the power supply is turned off because they are stored in the fixed memory.

 

 

 

Table 10-4-1

 

 

Block distinction

 

Operation of diagnosis function

 

 

Check

 

Check

 

Air

 

Judgment and action

Block

Cause of operation

conditioner

Remarks

 

code

code

 

 

 

status

 

 

 

 

 

 

 

 

 

Indoor P.C.

 

Short-circuit or

Operation

Displayed when

1. Check the room temp. sensor.

 

board etc.

 

disconnection of the room

continues.

error is detected.

2. When the room temp. sensor is

 

 

 

temperature sensor

 

 

 

 

 

 

 

normal, check P.C. board.

 

 

 

(TA sensor).

 

 

 

 

 

 

 

 

 

 

 

Being out of place,

Operation

Displayed when

1. Check heat exchanger sensor.

 

 

 

disconnection, short-

continues.

error is detected.

2. When heat exchanger sensor is

 

 

 

circuit, or migration of

 

 

 

 

 

 

 

normal, check P.C. board.

 

 

 

heat exchanger sensor

 

 

 

 

 

 

 

 

 

 

 

(TC sensor)

 

 

 

 

 

 

Lock of indoor fan or

All off

Displayed when

1. Check P.C. board.

 

 

 

trouble on the indoor fan

 

error is detected.

2. When P.C. board is normal, check

 

 

 

circuit

 

 

 

 

 

 

 

the motor.

 

 

 

 

 

 

 

Not

 

Trouble on other indoor

Operation

Displayed when

Replace P.C. board.

 

displayed

 

P.C. boards

continues.

error is detected.

 

 

Connecting

 

Return serial signal is not

Operation

Flashes when

1. When the outdoor unit never

 

cable and

 

sent to indoor side from

continues.

trouble is detected

operate:

 

serial signal

 

operation started.

 

on Return serial

(1) Check connecting cable, and

 

 

 

 

 

signal, and normal

 

 

 

(1) Defective wiring of

 

correct if defective wiring.

 

 

 

 

status when signal

 

 

 

connecting cable

 

 

 

 

 

 

is reset.

(2) Check 25A fuse of inverter P.C.

 

 

 

 

 

 

 

 

(2) Operation of

 

 

board.

 

 

 

compressor thermo.

 

 

(3) Check 3,15A of inverter P.C.

 

 

 

Gas shortage

 

 

 

 

 

 

 

board.

 

 

 

Gas leak

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. To display [Other] block during

 

 

 

 

 

 

operation, check compressor

 

 

 

 

 

 

thermo. operation and supply gas

 

 

 

 

 

 

(check gas leak also).

 

 

 

 

 

 

3. Unit operates normally during check.

 

 

 

 

 

 

If Return serial signal does not stop

 

 

 

 

 

 

between indoor terminal board 2 and

 

 

 

 

 

 

3, replace inverter P.C. board.

 

 

 

 

 

 

If signal stops between indoor

 

 

 

 

 

 

terminal board 2 and 3, replace

 

 

 

 

 

 

indoor P.C. board.

 

 

 

Operation command

Operation

Flashes when

If Return serial signal does not stop

 

 

 

signal is not sent to

continues

trouble is detected

between indoor terminal board 2 and 3,

 

 

 

outdoor side.

 

on Operation

replace inverter P.C. board.

 

 

 

 

 

command signal,

If signal stops between indoor terminal

 

 

 

 

 

and normal status

board 2 and 3, replace indoor P.C.

 

 

 

 

 

when signal is

board.

 

 

 

 

 

reset.

 

– 44 –