Toshiba RAS-13YKV-E, RAS-10YKV-E, RAS-10YAV-E, RAS-13YAV-E Cause, Confirmation procedure

Models: RAS-13YAV-E RAS-10YAV-E RAS-10YKV-E RAS-13YKV-E

1 79
Download 79 pages 58.17 Kb
Page 48
Image 48
<Cause>

(4)Indoor fan motor starts rotating by turning on power supply alone

(Operation may be normally performed (selected) by operation on the remote controller.)

<Cause>

IC is built in the indoor fan motor, therefore P.C. board is also mounted to inside of the motor.

If soldering of P.C. board in the motor is defective or IC is defective, the fan motor may rotate by only inputting the power (turning on power supply).

<Confirmation procedure>

(1)Remove the front panel.(Remove 2 screws and clicks.)

(2)Remove cover of the fan motor lead wire. (1 click)

(3)Check the voltage (DC) using CN10 connector while the fan rotates.

NOTE :

Do not disconnect the connector while the fan rotates.

Use a thin tester rod.

Indoor fan starts rotating when power supply breaker is turned "ON".

(Check output voltage (DC) of the fan motor on P.C. board.)

Measure the voltage of the motor connector

CN10 pin 2 (GND : Black) and pin 3 (V line : Yellow) under condition that the indoor fan rotates.

P.C. board

 

CN10

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Blue

 

 

 

 

 

 

 

 

 

Yellow

 

 

 

 

 

 

 

 

 

 

3

Yellow

 

 

 

 

 

Black

 

 

 

 

 

2

Black

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Red

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Above DC 0.4V

Below DC 0.4V

DC

P.C. board is defective.

Motor is defective.

– 48 –