Toshiba RAS-10YKV-E, RAS-13YKV-E, RAS-10YAV-E, RAS-13YAV-E service manual Primary Judgment

Models: RAS-13YAV-E RAS-10YAV-E RAS-10YKV-E RAS-13YKV-E

1 79
Download 79 pages 58.17 Kb
Page 41
Image 41

10-1-3. Operation Which is not a Trouble (Program Operation)

For controlling the air conditioner, the program operations are built in the microcomputer as described in the following table. If a claim is made for running operation, check whether or not it meets to the contents in the following table. When it does, we inform you that it is not trouble of equipment, but it is indispensable for control- ling and maintaining of air conditioner.

 

Table 10-1-1

 

 

 

No.

Operation of air conditioner

Description

 

 

 

1

When power breaker is turned “ON”, the

The OPERATION lamp of the indoor unit flashes when

 

operation lamp (Green) of the indoor unit

power source is turned on. If [START/STOP] button is

 

flashes.

operated once, flashing stops. (Flashes also in power

 

 

failure)

 

 

 

2

Compressor may not operate even if the

The compressor does not operate while compressor

 

room temperature is within range of

restart delay timer (3-minutes timer) operates.

 

compressor-ON.

The same phenomenon is found after power source has

 

 

been turned on because 3-minutes timer operates.

 

 

 

3

In Dry and ECONO. mode, FAN (air flow)

The air flow indication is fixed to [AUTO].

 

display does not change even though FAN

 

 

(air flow select) button is operated.

 

 

 

 

4

Increasing of compressor motor speed

For smooth operation of the compressor, the compressor

 

stops approx. 30 seconds after operation

motor speed is restricted to Max. 41 rps for 2 minutes, and

 

started, and then compressor motor speed

Max.91 rps for 2 minutes to 3 minutes, respectively after

 

increases again approx. 30 seconds after.

the operation has started.

 

 

 

5

The set value of the remote controller

If the set value is above the room temperature, Cooling

 

should be below the room temperature.

operation is not performed. And check whether battery of

 

 

the remote controller is consumed or not.

 

 

 

6

In AUTO mode, the operation mode is

After selecting Cool or Heat mode, select an operation

 

changed.

mode again if the compressor keeps stop status for 15

 

 

minutes.

 

 

 

7

In HEAT mode, the compressor motor

The compressor motor speed may decrease by high-temp.

 

speed does not increase up to the maxi-

release control (Release protective operation by temp.-up

 

mum speed or decreases before the

of the indoor heat exchanger) or current release control.

 

temperature arrives at the set tempera-

 

 

ture.

 

 

 

 

10-2. Primary Judgment

To diagnose the troubles, use the following methods.

(1)Judgment by flashing LED of indoor unit

(2)Self-diagnosis by service check remote controller

(3)Judgment of trouble by every symptom

Firstly use the method (1) for diagnosis. Then, use the method (2) or (3) to diagnose the details of troubles.

– 41 –