Toshiba RAS-13YKV-E, RAS-10YKV-E, RAS-10YAV-E, RAS-13YAV-E Installation Procedure, Danger

Models: RAS-13YAV-E RAS-10YAV-E RAS-10YKV-E RAS-13YKV-E

1 79
Download 79 pages 58.17 Kb
Page 36
Image 36
9. INSTALLATION PROCEDURE

9. INSTALLATION PROCEDURE

9-1. Safety Cautions

CAUTION New Refrigerant Air Conditioner Installation

• This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.

R410A refrigerant is apt to be affected by impurity such as water, oxidizing membrane, and oils because pressure of R410A refrigerant is approx. 1,6 times of refrigerant R22. Accompanied with adoption of the new refrigerant, refrigerating machine oil has been also changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating machine oil does not enter into the refrigerating cycle of new-refrigerant air conditioner.

To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port of the main unit or installation tools are different from those for the conventional refrigerant. Accordingly, the exclusive tools are required for the new refrigerant (R410A) as shown below.

For connecting pipes, use new and clean piping materials with high pressure-tight force, which were made for R410A only, so that water or dust does not enter. Moreover, do not use the existing piping because there are problems about pressure-tight force and inner impurity in the existing piping.

Power supply cord of parts of appliance for outdoor use shall be more

For general public use than polychloroprene sheathed flexible cord (design H07 RN-F), or cord designation 245 IEC 66. (2,0mm² or more)

Remark per EMC Directive 89/336/EEC

For to prevent flicker impressions during the start of the compressor (technical process) following installation conditions do apply.

1.The power connection for the air conditioner has to be done at the main power distribution. This distribution has to be of an impedance.

Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!

2.No other equipment has to be connected to this power line.

3.For detailed installation acceptance please refer to your contact with the power supplier, it restriction do apply for products like washing machines, air conditioners or electrical ovens.

4.For power details of the air conditioner refer to the rating plate of the product.

9-1-1. Installation Diagram of Indoor and Outdoor Units

CAUTION To Disconnect the Appliance from the Mains Supply.

This appliance must be connected to the mains by means of a circuit breaker or a switch with a contact separation of at least 3 mm.

If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after installation. The plug must be disconnected from the power supply socket in order to disconnect the appliance completely from the mains.

DANGER

Clip anchor

Hook

 

120

mm

 

 

 

 

Front cabinet

 

or

more

 

 

 

 

 

Front panel

66 mm or more

Hook

1Installation plate

For the rear left and left piping

Wall

Insert the cushion between the indoor unit and wall, and lift indoor unit to make work easier.

– 36

• FOR USE BY QUALIFIED PERSONS ONLY.

• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER

SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.

• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED BY WRONG

Hook

120

mm

 

or

 

 

 

more

5 Mounting screw

Do not allow the drain hose to get slack.

WAY, ELECTRIC PARTS MAY BE DAMAGED.

• CHECK THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.

Air filter

Cut the piping hole sloped slightly

• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.

FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.

• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY

(MORE THAN 2M.) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT REGISTORS, FURNACE, STOVES, ETC.

• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY CAREFUL

NOT TO GET THE SPECIFIED REFRIGERANT (R-22) WITH ANY OTHER GASEOUS BODY INTO THE REFRIG-

ERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE

(Attach

 

 

to

 

 

the

front

 

 

cabinet)

 

 

 

 

(Attach

7Deodorizing filter

to

 

 

the

front

 

 

cabinet)

 

 

Pan head wood screw

8

Shield pipe

Make sure to run the drain hose sloped downward.

The auxiliary piping can be

REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE

AND INJURIES ON PERSONS.

• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION WORK,

IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR

SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.

WARNING

Never modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches.

Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if

6 Purifying filter

2 Wireless remote controller

100mm

 

more

from

 

or

 

 

wall

 

4 Remote

 

 

controller

or more

 

holder

 

 

600mm

or

more

wall

50mmfrom

 

 

connected the left, rear left, rear, right or bottom.

Right

Rear

Rear left

BottomLeft

 

the unit falls.

Before doing the electrical work, attach an approved plug to the power supply cord. And make sure the equipment to

 

be earthed.

Appliance shall be installed in accordance with national wiring regulations.

 

If you detect any damage, do not install the unit. Contact your Toshiba dealer immediately.

CAUTION

Exposure of unit to water or other moisture before installation will result in an electrical short.

 

Do not store in a wet basement or expose to rain or water.

After unpacking the unit, examine it carefully for possible damage.

Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise

 

level of the unit or where noise and discharged air might disturb user’s neighbors.

To avoid personal injury, be careful when handling parts with sharp edges.

Before install the wireless remote controller

With the remote controller cover open, load the batteries supplied correctly, observing their polarity.

2 Wireless remote controller

3 DANGERManual backgroundManual backgroundManual background Batteries

Manual background Cover

more or m 200m Manual background

250mm

 

more

from

 

or

 

 

wall

Insulation of refrigerant pipes insulates the pipes separately, not together.

6 mm thick heat resisting polyethylene foam

• Please read the installation manual carefully before installing the unit. It contains further important instructions for

proper installation.

As shown in the figure, hang power cord

 

and connecting cable downward, and

Fig. 9-1-1

take out it along piping connection port.

Page 36
Image 36
Toshiba RAS-13YKV-E, RAS-10YKV-E, RAS-10YAV-E, RAS-13YAV-E service manual Installation Procedure, Danger