Toshiba RAS-16GAVP-E, RAS-B16GKVP-E Packed Valve handling precautions, Wiring Connection

Models: RAS-10GAVP-E RAS-16GAVP-E RAS-13GAVP-E RAS-B10GKVP-E RAS-B13GKVP-E RAS-B16GKVP-E

1 116
Download 116 pages 47.53 Kb
Page 58
Image 58

Packed Valve handling precautions

Open the valve stem all the way; but do not try to open it beyond the stopper.

Securely tighten the valve stem cap with torque in the following table:

Gas side (Ø 12.7 mm)

50 to 62 N•m (5.0 to 6.2 kgf•m)

 

 

Gas side (Ø 9.52 mm)

33 to 42 N•m (3.3 to 4.2 kgf•m)

 

 

Liquid side (Ø6.35 mm)

14 to 18 N•m (1.4 to 1.8 kgf•m)

 

 

Service port

14 to 18 N•m (1.4 to 1.8 kgf•m)

 

 

Hexagonal wrench is required.

Fig. 10-4-10

10-4-5. Wiring Connection

1.Remove the valve cover, the electric parts cover and the cord clamp from the outdoor unit.

2.Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of indoor and outdoor unit.

3.Insert the power cord and the connecting cable fully into the terminal block and secure it tightly with screws.

4.Insulate the unused cords (conductors) from water entering in the outdoor unit. Locate them so that they do not touch any electrical or metal parts.

5.Secure the power cord and the connecting cable with the cord clamp.

6.Attach the electric parts cover and the valve cover on the outdoor unit.

Stripping length of connecting cable

Terminal block

1 2 3 L N

Connecting cable Power cord

Fig. 10-4-11

1

2 3

L N

10

 

 

10

 

10

 

 

 

40

10

 

40

30

30

 

 

Earth line

Connecting

Power cord

Earth line

cable

Fig. 10-4-12

Model RAS-

10GAVP-E

13GAVP-E

16GAVP-E

 

 

 

 

 

Power source

220 – 240 V

~50 Hz

 

220 V

~60 Hz

 

 

 

 

 

 

 

Maximum running

 

12 A

 

 

current

 

 

 

 

 

 

 

 

 

 

 

 

Installation fuse

25A (D type

)

rating

 

 

 

 

 

 

Power cord

H07RN-F or 245IEC66 (1.5 mm²)

 

 

Connection cable

H07RN-F or 245IEC66 (1.0 mm²)

 

 

 

 

 

CAUTION

Incorrect wiring connection may cause electri- cal parts to burn out.

Be sure to comply with local regulations/codes when running the wire from outdoor unit to indoor unit.

(Size of wire and wiring method etc.)

Every wire must be securely connected.

This installation fuse (25A D type ) must be used for the power supply line.

If incorrect or incomplete wiring is carried out, fire or smoke may result.

Prepare the power supply for the exclusive use of the air conditioner.

This product can be connected to the main breaker.

Connection to fixed wiring:

A switch which disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring when connect- ing to a main breaker circuit.