Toshiba RAS-16GAVP-E Operation flow and applicable data, etc, Description, Powerful, Auto Heat

Models: RAS-10GAVP-E RAS-16GAVP-E RAS-13GAVP-E RAS-B10GKVP-E RAS-B13GKVP-E RAS-B16GKVP-E

1 116
Download 116 pages 47.53 Kb
Page 34
Image 34

Item

9.Louver control

1)Louver position

Operation flow and applicable data, etc.

Description

This function controls the air direction of the indoor unit.

The position is automatically controlled according to the operation mode (COOL/HEAT).

The set louver position is stored in memory by the microcomputer, and the louver returns to the stored position when the next operation is performed. (Cooling/heating memory position)

The angle of the louver is indicated as the horizontal angle is 0°.

When the louver closes fully, it directs approx. 49° upward.

1) Louver position in cooling operation

Louver angle

Horizontal

(0˚)

 

Powerful

Room temp. (Ta) < Set temp. (Tsc) + 3.5

Room temp. (Ta) Set temp. (Tsc) + 3.5

Initial setting of “Cooling storage position” Louver : Directs downward (9˚)

Initial setting of “Cooling storage position” Louver : Directs downward (9˚)

“Inclined blowing”

Louver : Directs downward (14˚)

Cooling/AUTO (COOL)/DRY operation

 

 

Powerful YES

Room temp. NO

 

 

operation

 

Set temp. +3.5

 

 

 

 

 

 

 

 

NO

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

Cooling memory

 

 

 

 

 

 

position

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling memory

position

Inclined blowing

NO

Room temp. Set temp. +3.5

YES

2) Louver position in heating operation

Heating operation/

ECO operation

Room temp. (Ta) < Set temp. (Tsc) – 3

Room temp. (Ta) Set temp. (Tsc) – 3

AUTO (HEAT)

or 25 minutes after start of operation

 

 

 

Initial setting of “Heating storage position” Louver : Directs downward (76˚)

“Heating storage position” Louver : Directs downward (76˚)

“Cooling storage position” Louver : Directs downward (9˚)

Heating operation

 

 

ECO YES

Room temp. NO

 

 

 

 

operation

 

Set temp. –3.0

 

 

 

NO

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating memory

 

 

 

 

 

 

position

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal

position

Heating memory

position

NO

Room temp. Set temp. –3.0

YES

2) Air direction adjustment

Air direction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal

 

Inclined

 

Blowing

 

Inclined

 

Horizontal

 

 

 

 

blowing

 

blowing

 

downward

 

blowing

 

blowing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) Swing

Swing operation is performed in width 35° with the stop position as

 

 

the center.

 

If the stop position exceeds either upper or lower limit position,

 

 

swing operation is performed in width 35° from the limit which the

 

 

stop position exceeded.

 

 

 

The louver position can be arbitrarily set up by pressing [FIX] button.

Swing

When pressing [SWING] button during operation, the louver starts swinging.

– 34 –

Page 34
Image 34
Toshiba RAS-16GAVP-E Operation flow and applicable data, etc, Description, Louver position in cooling operation, Powerful