r3 Writing of the setup contents to EEPROM

(The contents of EEPROM installed on the service P.C. board have been set up at shipment from the factory.)

1.Push SET , CL , and TEST buttons of the remote controller at the same time for 4 seconds or more. 1 (Corresponded with No. in Remote controller )

In group operation control, the master indoor unit No. is displayed at the first time. (If the automatic address setup mode is interrupted in item 2. - a) - 2) in the previous page, the unit No. ALL is displayed.) In this time, the item code (DN) 10 is displayed. The fan of the selected indoor unit operates and the louver starts swinging if any.

2. Every pushing UNIT button, the indoor unit numbers in the group control are displayed successively. 2 Specify the indoor unit No. of which P.C. board has been replaced with a service P.C. board.

(When the unit No. ALL is displayed, this operation cannot be performed.)

3.Using the set temperature / buttons, the item code (DN) can be moved up and down one by one. 3

4.First set a type and capacity of the indoor unit.

(Setting the type and capacity writes the data at shipment from the factory in EEPROM.)

1)Set the item code (DN) to 10. (As it is)

2)Using the timer time / buttons, set up a type. 4

(For example, 4-way air discharge cassette type is 0001) Refer to the attached table.

3)Push SET button. (OK when the display goes on.) 5

4)Using the set temperature / buttons, set 11 to the item code (DN).

5)Using the timer time / buttons, set the capacity.

(For example, 0012 for class 80) Refer to the attached table.

6)Push SET button. (OK when the display goes on.)

7)Push TEST button to return the status to usual stop status. 6

(Approx. 1 minute is required to start handling of the remote controller.)

5.Next write the contents which have been set up at the local site such as the address setup in EEPROM. Repeat the above procedure 1. and 2.

6.Using the set temperature / buttons, set 01 to the item code (DN). (Setup of lighting time of filter sign)

7.The contents of the displayed setup data in this time should be agreed with the contents in the previous memorandum in r1.

1)If data disagree, change the displayed setup data to that in the previous memorandum by the timer time / buttons, and then push SET button. (OK when the display goes on.)

2)There is nothing to do when data agrees.

8.Using the set temperature / buttons, change the item code (DN).

As same as the above, check the contents of the setup data and then change them to data contents in the previous memorandum.

9.Then repeat the procedure 7. and 8.

10.After completion of setup, push TEST button to return the status to the usual stop status. 6

(Approx. 1 minute is required to start handling of the remote controller.)

*01 to 9F are provided in the item code (DN). On the way of operation, DN No. may come out.

When data has been changed by mistake and SET , button has been pushed, the data can be

returned to the data before change by pushing CL button if the item code (DN) was not yet changed.

3

4

6

<REMOTE CONTROLLER>

SET DATA

 

 

UNIT No.

 

R.C.

No.

 

TEMP.

 

ON / OFF

TIMER SET

FAN

MODE

TIME

SWING/FIX

VENT

FILTER

 

5

RESET TEST SET CL

UNIT

 

1

2

– 103 –

Page 103
Image 103
Toshiba RAV-SM562UT-E, RAV-SM1102UT-E, RAV-SM1402UT-E, RAV-SM802UT-E service manual R3 Writing of the setup contents to Eeprom

RAV-SM562UT-E, RAV-SM802UT-E, RAV-SM1402UT-E, RAV-SM1102UT-E specifications

Toshiba has established itself as a leading name in the field of heating, ventilation, and air conditioning (HVAC) systems. Among their extensive range, the RAV-SM802UT-E, RAV-SM1102UT-E, RAV-SM1402UT-E, and RAV-SM562UT-E stand out for their performance, efficiency, and innovative technology.

The Toshiba RAV-SM802UT-E is designed for medium-sized commercial spaces, providing a cooling capacity of 8 kW. It employs advanced inverter technology, which enables it to adjust the compressor speed based on the load demand. This adaptability leads to a significant decrease in energy consumption, making the unit both eco-friendly and cost-effective. The unit also features a high-efficiency rotary compressor and a wide operating temperature range, ensuring reliable performance even in extreme weather conditions.

Next in line, the RAV-SM1102UT-E offers an impressive 11 kW cooling capacity, making it suitable for larger commercial applications. This model incorporates Toshiba’s cutting-edge Superlink technology, which allows multiple indoor units to be connected to a single outdoor unit, providing flexible installation options. The RAV-SM1102UT-E is also equipped with a sleek and modern design that blends seamlessly with any architecture while ensuring low noise levels during operation, enhancing comfort in the workspace.

The RAV-SM1402UT-E is a powerhouse among the series, boasting a cooling capacity of 14 kW. It is built with an enhanced refrigerant management system that minimizes refrigerant leaks and optimizes thermal efficiency. This model supports smart building management systems, making it an ideal choice for tech-savvy businesses looking to integrate their HVAC systems into a broader energy management framework. Furthermore, it maintains high EU energy efficiency ratings, verifying Toshiba's commitment to environmental sustainability.

Lastly, the RAV-SM562UT-E, with its 5.6 kW cooling capacity, is tailored for smaller commercial environments and residential use. It retains all the core technologies featured in its counterparts, including inverter technology and a high-efficiency compressor, ensuring comfort without excessive energy usage. This model also includes a user-friendly remote control and programmable timer functions, allowing for customized comfort settings and enhanced convenience.

In summary, the Toshiba RAV-SM series represents the pinnacle of HVAC innovation, blending energy efficiency with advanced technology. Each model caters to specific needs, from the compact RAV-SM562UT-E to the robust RAV-SM1402UT-E, ensuring that every commercial and residential space can achieve optimal climate control.