Toshiba RAV-SM562UT-E, RAV-SM1102UT-E, RAV-SM1402UT-E Revised : Nov, Indoor unit, Outdoor unit, 35

Models: RAV-SM562UT-E RAV-SM802UT-E RAV-SM1402UT-E RAV-SM1102UT-E

1 196
Download 196 pages 53.59 Kb
Page 35
Image 35
– 35 –

Revised : Nov. 2006

RAV-SM562UT-E, RAV-SM562BT-E, RAV-SM562CT-E / RAV-SP562AT-E

Outer diameter of refrigerant pipe

Gas side ØA

Liquid side ØB

 

 

12.7mm

6.4mm

 

 

Indoor unit

TCJ

sensor

Air heat exchanger

TC sensor

* The refrigerating cycle of the indoor units differs according to the models to be combined. For the refrigerating cycles of the other indoor units, refer to the corresponding Service Manuals described in the list on the cover.

 

 

Refrigerant pipe

 

Refrigerant pipe

 

 

 

 

at gas side

 

at liquid side

 

 

 

 

Outer dia. ØA

 

Outer dia. ØB

 

 

 

 

 

 

 

 

 

 

 

Min.

 

Max.

 

 

 

 

5m

 

50m

Pd

 

Packed valve

 

Packed valve

 

Ps

 

 

 

 

 

Outer dia. ØA

Outdoor unit

Outer dia. ØB

 

 

 

 

 

 

 

 

TS sensor

 

Strainer

 

Modulating

 

 

 

 

(PMV)

 

 

 

 

 

 

 

 

TO sensor

(SKV-18D26)

 

TD sensor

 

 

Strainer

Accumulator (1500cc)

4-way valve Muffler (STF-0213Z)

Manual backgroundØ25 × L210 Ø25 × L160

TE sensor

Heat exchangerØ8 1 row 30 stages FP1.3 flat fin

Capillary Ø3×Ø 2× L530

 

 

Rotary compressor

 

 

 

 

 

 

 

 

 

(DA220A2F-20L)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R410A 1.5 kg

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

Heating

 

 

Pressure

 

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

Indoor

temp. conditions

 

 

 

(MPa)

 

 

Indoor heat

Outdoor heat

revolutions per

 

 

 

Discharge

Suction

(DB/WB) (°C)

 

 

 

fan

 

 

 

second (rps)

 

 

 

 

exchanger

exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

Pd

Ps

(TD)

(TS)

(TC)

(TE)

*

 

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.71

1.03

75

15

10

38

43

HIGH

27/19

35/–

Cooling

Overload

3.48

1.16

81

20

16

51

44

HIGH

32/24

43/–

 

Low load

1.92

0.74

34

5

2

11

24

LOW

18/15.5

–5/–

 

Standard

2.22

0.72

32

6

38

2

41

HIGH

20/–

7/6

Heating

Overload

3.47

1.16

81

20

55

15

41

LOW

30/–

24/18

 

Low load

1.79

0.25

71

–16

30

–18

70

HIGH

15/–

–15/(70%)

*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.