Toshiba RAV-SM802UT-E, RAV-SM1102UT-E, RAV-SM1402UT-E, RAV-SM562UT-E 1 2 END, 1 2 3 END, 118

Models: RAV-SM562UT-E RAV-SM802UT-E RAV-SM1402UT-E RAV-SM1102UT-E

1 196
Download 196 pages 53.59 Kb
Page 118
Image 118
1  2 END

nConfirmation of indoor unit No. position

1. To k now th e indoor unit addresses th ough position of th e indoor unit body is recognized

In case of individual operation (Wired remote controller : indoor unit = 1 : 1) (Follow to the procedure during operation)

<Procedure>

 

1

Push

ON / OFF button if th e unit stops.

2

Push

UNIT

button.

 

Unit No. 1-1is displayed on LCD.

(It disappears after several seconds.)

The displayed unit No. indicate line address and indoor unit address.

(When other indoor units are connected to the identical remote controller (Group control unit), other unit numbers are also displayed every pushing UNIT button.

UNIT No.

TEMP.

 

ON / OFF

TIMER SET

FAN

MODE

TIME

SWING/FIX

VENT

FILTER

 

 

RESET TEST SET CL

UNIT

 

<Operation procedure>

1

Operation

2

1 1  2  3 END 2 END

2. To k now th e position of indoor unit body by address

To confirm the unit No. in the group control

(Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)

<Procedure>

The indoor unit numbers in the group control are succes- sively displayed, and fan, louver, and drain pump of the corresponding indoor unit are turned on.

(Follow to the procedure during operation)

1 Push VENT and TEST buttons simultaneously for

4 seconds or more.

Unit No. ALL is displayed.

Fans and louvers of all the indoor units in the group control operate.

2 Every push ingUNIT button, th e unit numbers in th e group control are successively dis- play ed.

The unit No. displayed at the first time indicates the master unit address.

Fan and louver of the selected indoor unit only operate.

3 Push TEST button to finish th e procedure.

All th e indoor units in th e group control stop.

 

SET DATA

 

 

 

 

 

UNIT

No.

 

 

 

R.C.

No.

 

 

TEMP.

 

 

ON / OFF

1

TIMER SET

 

FAN

MODE

TIME

SWING/FIX

VENT

 

 

FILTER

 

 

 

 

RESET TEST SET CL

 

UNIT

 

3

 

 

 

2

<Operation procedure>

1 – 118 – 2 Manual background 3 END

– 118 –

Page 118
Image 118
Toshiba RAV-SM802UT-E, RAV-SM1102UT-E, RAV-SM1402UT-E, RAV-SM562UT-E service manual 1 2 END, 1 2 3 END, 118