15
18
21
24
TE [˚C]
+1 tap/20 seconds
rpm hold
–1 tap/20 seconds
–2 tap/20 seconds
–2 tap/20 seconds STOP timer count

2)Heating fan control

Q The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency. (From Min. W1 to Max. are controlled according to the following table.)

R During 3 minutes after start-up, the fan is fixed

with the maximum fan tap corresponding to zone in the following table. After then the fan is controlled by temperature of TE sensor.

S If status, TE > 24°C continues for 5 minutes, the operation stops. This status is same to the usual Thermo-OFF which has no alarm display, and the fan restarts after 2 minutes and 30 seconds. This intermittent operation is not abnormal.

T When the above status R occurs frequently, it is considered that the filter of suction part of the indoor unit is stain. Clean the filter and then restart the operation.

(The operation frequency differs according to the model type. The case of SM1102 is shown in the table below.)

 

Temp. range

Below 33 Hz

Above 33 Hz below 51 Hz

Above 51 Hz

 

 

 

 

 

 

10°C < TO

W7

W8

W9

Maximum

5 < TO < 10°C

WA

WB

WF

TO < 5°C

WF

WF

WF

 

 

 

 

 

 

 

TO error

WF

WF

WF

 

 

 

 

 

5.Coil heating control

1)This control function heats the compressor by turning on the stopped compressor instead of a case heater. It purposes to prevent slackness of the refrigerant inside of the compressor.

2)As usual, turn on power of the compressor for the specified time before a test run after installation, otherwise a trouble of the compressor may be caused. As same as a test run, it is recommended to turn on power of the compressor beforehand when starting operation after power of the compressor has been interrupted for a long time.

3)A judgment for electricity is performed by TD and TO sensors. If TO sensor is defective, a backup control is automatically performed by TE sensor. For a case of defective TO sensor, judge it with the outdoor LED display.

4)Coil heating is controlled by TD and TE sensor.

5)For every model, the power is turned off when TD is 30°C or more.

(In trouble of TE sensor)

TO [˚C]

18

Power-ON condition 15

TD < 30˚C10

8

 

TE [˚C]

No power-ON

20

18

 

Continuous ON (L)

12

 

10

Continuous ON (M)

 

No power-ON

Continuous ON (L)

Continuous ON (M)

* TD sensor is read in once per 15 minutes.

* TO sensor is read in once per 15 minutes

(Object: SM562, SM802)

TE [˚C]

0

 

No power-ON

 

–1

 

 

–6

 

Continuous ON (L)

–7

 

 

 

 

Continuous ON (H)

 

 

 

 

 

 

SM1102, SM1402

L20W and equivalent

M 40W and equivalent

SM562, SM802

L10W and equivalent

H 30W and equivalent

– 77 –

Page 77
Image 77
Toshiba RAV-SM1402UT-E, RAV-SM1102UT-E Coil heating control, Trouble of TE sensor, To ˚C, Te ˚C, Object SM562, SM802

RAV-SM562UT-E, RAV-SM802UT-E, RAV-SM1402UT-E, RAV-SM1102UT-E specifications

Toshiba has established itself as a leading name in the field of heating, ventilation, and air conditioning (HVAC) systems. Among their extensive range, the RAV-SM802UT-E, RAV-SM1102UT-E, RAV-SM1402UT-E, and RAV-SM562UT-E stand out for their performance, efficiency, and innovative technology.

The Toshiba RAV-SM802UT-E is designed for medium-sized commercial spaces, providing a cooling capacity of 8 kW. It employs advanced inverter technology, which enables it to adjust the compressor speed based on the load demand. This adaptability leads to a significant decrease in energy consumption, making the unit both eco-friendly and cost-effective. The unit also features a high-efficiency rotary compressor and a wide operating temperature range, ensuring reliable performance even in extreme weather conditions.

Next in line, the RAV-SM1102UT-E offers an impressive 11 kW cooling capacity, making it suitable for larger commercial applications. This model incorporates Toshiba’s cutting-edge Superlink technology, which allows multiple indoor units to be connected to a single outdoor unit, providing flexible installation options. The RAV-SM1102UT-E is also equipped with a sleek and modern design that blends seamlessly with any architecture while ensuring low noise levels during operation, enhancing comfort in the workspace.

The RAV-SM1402UT-E is a powerhouse among the series, boasting a cooling capacity of 14 kW. It is built with an enhanced refrigerant management system that minimizes refrigerant leaks and optimizes thermal efficiency. This model supports smart building management systems, making it an ideal choice for tech-savvy businesses looking to integrate their HVAC systems into a broader energy management framework. Furthermore, it maintains high EU energy efficiency ratings, verifying Toshiba's commitment to environmental sustainability.

Lastly, the RAV-SM562UT-E, with its 5.6 kW cooling capacity, is tailored for smaller commercial environments and residential use. It retains all the core technologies featured in its counterparts, including inverter technology and a high-efficiency compressor, ensuring comfort without excessive energy usage. This model also includes a user-friendly remote control and programmable timer functions, allowing for customized comfort settings and enhanced convenience.

In summary, the Toshiba RAV-SM series represents the pinnacle of HVAC innovation, blending energy efficiency with advanced technology. Each model caters to specific needs, from the compact RAV-SM562UT-E to the robust RAV-SM1402UT-E, ensuring that every commercial and residential space can achieve optimal climate control.