3. Cord heater installation wiring diagram

3. Cord heater installation wiring diagram

LN

Fuse

Thermostat

Cord heater

* Be sure to connect the fuse and the thermostat to LIVE side of the cord heater.

Outdoor unit

– 186 – Earth leakage circuit breaker Manual background Power supply for air conditioner

 

Earth leakage circuit breaker

 

Power supply for cord heater

 

 

 

 

 

 

 

 

NOTE:

Separate the cord heater power from the air conditioner power, and connect it to its exclusive breaker.

By doing so, the power consumption can be decreased because the breaker can be turned off if there is no possibility of freezing of the base plate in cooling operation, etc.

When the cord heater power is connected to the inverter P.C. board assembly or others without connected to the exclusive breaker, the control P.C. board of the inverter assembly may cause a failure.

When the cord heater has been mounted on a base plate, do not mount the water-proof cap and drain nipple which are provided with the outdoor unit on the base plate.

– 186 –