Toshiba RAV-SM1402UT-E, RAV-SM1102UT-E, RAV-SM802UT-E, RAV-SM562UT-E Indoor unit, 37, Outdoor unit

Models: RAV-SM562UT-E RAV-SM802UT-E RAV-SM1402UT-E RAV-SM1102UT-E

1 196
Download 196 pages 53.59 Kb
Page 37
Image 37
Outdoor unit

RAV-SM1102UT-E, RAV-SM1102BT-E, RAV-SM1102CT-E / RAV-SP1102AT-E

Outer diameter of refrigerant pipe

Gas side ØA

Liquid side ØB

 

 

15.9mm

9.5mm

 

 

Indoor unit

TCJ sensor

Distributor

(Strainer incorporated)

Strainer

 

Air heat exchanger

 

 

TC sensor

*The refrigerating cycle of the indoor units differs according to the models to be combined. For the refrigerating cycles of the other indoor units, refer to the corresponding Service Manuals described in the list on the cover.

 

Refrigerant pipe

 

 

at gas side

 

 

Outer dia. Ø A

 

 

Ball valve

 

 

Outer dia. Ø A

Outdoor unit

 

Strainer

 

 

TS sensor

Check joint

 

TO sensor

TD sensor

TE sensor

4-way valve

(STF-0401G)

Refrigerant pipe at liquid side Outer dia. Ø B

Min. Max. 5m 70m

Packed valve Outer dia. Ø B

PMV (UKV-25D22)

– 37 – Strainer

 

 

 

 

 

Heat exchanger

 

 

 

Muffler

 

 

Distributor

 

 

 

 

2 row 52 stages

 

 

 

 

 

 

 

 

 

 

 

 

Ø 25 ×

L210

Outside :

 

 

Ø 8 FP1.3 flat fin

 

 

Ø 25 ×

L180

Inside :

 

Accumulator

Ø 9.52 FP1.5 flat fin

 

Rotary

 

 

 

 

 

(2500cc)

compressor

 

 

 

 

(DA420A3F – 21M)

 

 

 

 

 

 

R410A 2.95kg

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

Heating

 

 

Pressure

 

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

Indoor

temp. conditions

 

 

 

(MPa)

 

 

Indoor heat

Outdoor heat

revolutions per

 

 

 

Discharge

Suction

(DB/WB) (°C)

 

 

 

fan

 

 

 

second (rps)

 

 

 

 

exchanger

exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

Pd

Ps

(TD)

(TS)

(TC)

(TE)

*

 

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.55

0.98

69

12

10

40

40

HIGH

27/19

35/–

Cooling

Overload

3.28

1.08

82

17

16

48

50

HIGH

32/24

43/–

 

Low load

1.76

0.76

47

8

5

27

24

LOW

18/15.5

–5/–

 

Standard

2.58

0.73

68

3

40

3

44

HIGH

20/–

7/6

Heating

Overload

3.43

1.18

75

20

56

16

24

LOW

30/–

24/18

 

Low load

2.10

0.32

88

–14

34

–13

63

HIGH

15/–

–15/(70%)

*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

– 37 –

Page 37
Image 37
Toshiba RAV-SM1402UT-E, RAV-SM1102UT-E, RAV-SM802UT-E, RAV-SM562UT-E service manual Indoor unit, 37, Outdoor unit