12-2. Setup at Local Site / Oth ers

12-2. Setup at Local Site / Oth ers

Model name: TCB-PCNT30TLE2

12-2-1. TCC-LINK Adapter (For TCC-LINK Central Control)

1.Function

This model is an optional P.C. board to connect the indoor unit to TCC-LINK (Central controller).

2.Microprocessor Block Diagram

Indoor unit

 

TCC-LINK adapter P.C. board

CN40

 

 

 

CN050

CN51

 

 

Indoor control

TCC-LINK

Terminal

P.C. board

 

communication circuit

resistance

CN041

 

 

 

 

 

 

SW01

Terminal block

 

 

MCC-1440

(A, B)

 

 

 

Remote controller

Central

controller

TCC-LINK

Communication units: Total 64 units

Communication distance: 2km

3. TCC-LINK Wiring Connection

CAUTION

1)When controlling customized setup collectively, TCC-LINK adapter (This option) is required.

2)In case of group operation or twin/triple operation, the adapter is necessary to be connected to the main unit.

3)Connect the central control devices to the central control system wiring.

4)When controlling collectively customized setup only, turn on only Bit 1 of SW01 of the least line of the system address No. (OFF when shipped from the factory)

In case of customized setup, th e address is necessary to be set up again from th e wired remote controller after automatic addressing.

Central control device

 

U1

U2

 

 

U3

U4

 

Central control device

 

U1

U2

 

 

U3

U4

 

Central control devices: Max. 10 units

Refrigerant line 1

Refrigerant line 2

Refrigerant line 3

Outdoor unit

Refrigerant line 4

1 2 3

Caution 3

Indoor unit

U3 U4

1

2

3

 

 

 

A B

 

TCC-LINK adapter

 

 

 

 

This product

 

 

 

 

( sold separately )

Caution 1

 

 

 

1

2

3

1

2

3

 

 

 

Maater

 

 

Sub

 

 

 

unit

 

 

unit

U3 U4

1

2

3

1

2

3

 

 

A B

 

A B

Caution 2

Remote controller wiring

 

 

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor/outdoor inter-unit wire (AC200V serial)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Central control system wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Wiring for No.1 and 2 only

 

 

 

 

 

 

 

 

 

 

Sub unit

 

 

 

 

 

 

 

 

Maater unit

 

 

Sub unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

 

 

U3 U4

 

1

 

2

 

3

 

 

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

A B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

Remote controller

Remote controller

Remote controller

Group operation (Max. 8 units)Twin/Triple operation (Example of triple)

Indoor units in all refrigerant lines: Max. 64 units

[If mixed with multi model (Link wiring), multi indoor units are included.]

* However group sub units and twin/triple sub units of customized setup are not included in number of the units.