Toshiba RAV-SM562UT-E Systematic Refrigerating Cycle Diagram, Revised : Nov, Indoor unit, 31

Models: RAV-SM562UT-E RAV-SM802UT-E RAV-SM1402UT-E RAV-SM1102UT-E

1 196
Download 196 pages 53.59 Kb
Page 31
Image 31
Revised : Nov. 2006

Revised : Nov. 2006

4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM

4-1. Indoor Unit/Outdoor Unit

RAV-SM562UT-E, RAV-SM562BT-E, RAV-SM562CT-E / RAV-SM562AT-E

Indoor unit

Air heat exchanger

TC sensor

Outer diameter of refrigerant pipe

Gas side ØA

Liquid side ØB

 

 

12.7mm

6.4mm

 

 

TCJ sensor

Refrigerant pipe

Refrigerant pipe

at gas side

at liquid side

Ø12.7

Ø6.4

Packet valve

Packet valve

Min. Max. 5m 30m

 

Packed valve

 

Packed valve

 

Outer dia. ØA

Outdoor unit

Outer dia. ØB

 

 

 

TS sensor

 

 

PMV

 

 

(Pulse Motor Valve)

 

 

 

2-step muffler

TO sensor

 

(CAM-B30YGTF-1)

 

 

Ø19 .05 × 200L

 

 

 

TD sensor

 

 

 

 

 

 

Strainer

4-way valve

 

TE

 

(STF-0108Z)

 

sensor

 

Muffler

Heat exchanger

 

 

Ø19 × L160

Ø8 ripple, 2 rows,

 

 

14 steps

Distributor

 

FP1.3 flat fin

Rotary compressor

 

 

 

 

 

(DA150A1F-20F)

 

 

 

 

 

 

 

 

 

 

 

 

R410A 1.0 kg

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

 

 

Pressure

 

 

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

Indoor

temp. conditions

 

 

(MPa)

(kg/cm²G)

 

 

Indoor heat

Outdoor heat

revolutions per

 

 

Discharge

Suction

(DB/WB) (°C)

 

 

fan

 

 

second (rps)

 

 

 

 

 

 

exchanger

exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pd

Ps

Pd

Ps

(TD)

(TS)

(TC)

(TE)

*

 

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

3.50

0.97

35.7

9.9

85

14

12

48

70

HIGH

27/19

35/–

Cooling

Overload

3.90

1.08

39.8

11.0

93

26

17

54

70

HIGH

32/24

43/–

 

Low load

1.90

0.70

19.4

7.1

48

7

5

30

50

LOW

18/15.5

–5/–

 

Standard

2.31

0.61

13.6

6.2

87

5

40

1

97

HIGH

20/–

7/6

Heating

Overload

2.86

0.89

29.2

9.1

86

17

47

11

95

LOW

28/–

24/18

 

Low load

1.86

0.25

19.0

2.6

69

–14

31

–15

98

HIGH

15/–

–10/(70%)

*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

– 31 –
Page 31
Image 31