Toshiba RAV-SM1102UT-E, RAV-SM1402UT-E 104, Type Item code, Indoor unit capacity Item code

Models: RAV-SM562UT-E RAV-SM802UT-E RAV-SM1402UT-E RAV-SM1102UT-E

1 196
Download 196 pages 53.59 Kb
Page 104
Image 104

Memorandum for setup contents (Item code table (Example))

DN

Item

Memo

At shipment

 

 

 

 

01

Filter sign lighting time

 

According to type

 

 

 

 

02

Dirty state of filter

 

0000: Standard

 

 

 

 

03

Central control address

 

0099: Unfixed

 

 

 

 

06

Heating suction temp shift

 

0002: +2°C (Floor type: 0)

 

 

 

 

0F

Cooling only

 

0000: Shared for cooling/heating

 

 

 

 

10

Type

 

According to model type

 

 

 

 

11

Indoor unit capacity

 

According to capacity type

 

 

 

 

12

Line address

 

0099: Unfixed

 

 

 

 

13

Indoor unit address

 

0099: Unfixed

 

 

 

 

14

Group address

 

0099: Unfixed

 

 

 

 

19

Louver type (Adjustment of air direction)

 

According to type

 

 

 

 

1E

Temp difference of automatic cooling/

 

0003: 3 deg (Ts ± 1.5)

heating selecting control points

 

 

 

 

 

 

 

 

28

Automatic reset of power failure

 

0000: None

 

 

 

 

2A

Option

 

0002:

 

 

 

 

2b

Thermo output selection (T10 ‡ B)

 

0000: Thermo ON

 

 

 

 

2E

Option

 

0000:

 

 

 

 

32

Sensor selection

 

0000: Body sensor

 

 

 

 

5d

High ceiling selection

 

0000: Standard

 

 

 

 

60

Timer set (Wired remote controller)

 

0000: Available

 

 

 

 

8b

Correction of high heat feeling

 

0000: None

 

 

 

 

Type

Item code [10]

Setup data

Type

Abbreviated name

 

 

 

0001*

4-way air discharge cassette

RAV-SM562/802UT-E, RAV-SP1102UT-E

 

 

0038

RAV-SM1102/1402UT-E

 

 

 

 

0004

Concealed duct

RAV-SM562/802/1102/1402BT-E

 

 

 

0007

Under ceiling

RAV-SM562/802/1102/1402CT-E

 

 

 

* Initial setup value of EEPROM installed on the service P.C. board

Indoor unit capacity

Item code [11]

Setup data

SM562UT-E, SM562BT-E, SM562CT-E

SM802UT-E, SM802BT-E, SM802CT-E

 

 

 

0000*

Invalid

 

 

0009

562

 

 

0012

802

 

 

Setup data

RAV-SM1102UT-E, SM1402UT-E, SM1102BT-E, SM1402BT-E, SM1102CT-E, SM1402CT-E

RAV-SP1102UT-E

 

 

 

0000*

Invalid

 

 

0015

1102

 

 

0017

1402

 

 

* Initial setup value of EEPROM installed on the service P.C. board