E6581315

„Block Write 1, 2

Select data, which is desired to be written in block communication, in block write Data 1 and 2 Pa- rameters (, ). This parameter becomes effective when the system is reset, such as when power is turned off. When the setting is completed, turn off and then on the power.

No.

Block Write Data

For data details, see:

0

Deselect

1

Command information 1 (FA00)

 

2

Command information 2 (FA20)

 

3

Frequency Command (FA01)

“8.1 Command by communication”

4

Terminal board output data (FA50)

 

5

Communication analog output (FA51)

 

*When “Deselect” is specified in the parameters, no data will be written even though write data is specified.

„Block Read 1 to 5

Select read data, which is desired to be read in block communication, in block read data 1 and 5 Pa- rameters (to). This parameter becomes effective when the system is reset, such as when power is turned off. When the setting is completed, turn off and then on the power.

No.

Block Read Data

For data details, see:

0

Deselect

1

Status information (FD01)

 

2

Output frequency (FD00)

 

3

Output current (FD03)

 

4

Output voltage (FD05)

 

5

Alarm Information (FC91)

 

6

PID feedback value (FD22)

 

7

Input terminal board monitor (FD06)

“8.2 Monitoring from communication”

8

Output terminal board monitor (FD07)

 

9

V/II terminal boad monitor (FE36)

 

10

RR/S4 terminal board monitor (FE35)

 

11

RX terminal board monitor (FE37)

 

12

Input voltage (DC detection) (FD04)

 

13

Speed feedback frequency (FD16)

 

14

Torque (FD18)

 

15

My monitor 1(FE60)

16

My monitor 2(FE61)

17

My monitor 3(FE62)

18

My monitor 4(FE63)

19

Free notes (F880)

“7.5 Free notes ()”

*V/II terminal board monitor (FE36), RR/S4 terminal board monitor (FE35) and RX terminal board monitor (FE37) will become hold data during a trip. Otherwise, real-time data appears.

*“0000” will be returned as dummy data, if “0 (Deselect)” is selected for the parameter and “read” is specified.

14

Page 15
Image 15
Toshiba TOSVERT VF-AS1 instruction manual