Appendix 4 Troubleshooting

If a problem arises, diagnose it in accordance with the following table before making a service call. If the problem cannot be solved by any remedy described in the table or if no remedy to the problem is specified in the table, contact your Toshiba dealer.

Problem

 

 

Remedies

Reference

 

 

 

 

 

 

 

Communication

will

not

take

- Are both the computer and the inverter turned on?

 

 

place.

 

 

 

- Are all cables connected correctly and securely?

 

 

 

 

 

 

- Are the same baud rate, parity and bit length set for every unit on the

Chapter 7

 

 

 

 

network?

 

 

An error code is returned.

 

- Is the data transmission format correct?

Section 4.1

 

 

 

 

Section 5.1

 

 

 

 

- Does the data written fall within the specified range?

Chapter 9

 

 

 

 

 

- Some parameters cannot be written during inverter operation.

Inverter

 

 

 

 

 

Changing should be attempted when the inverter is in halt.

instruction

 

 

 

 

 

manual

 

The trip err5 and alarm t

- Check the cable connection and the timer setting.

Section 7.3

occur.

 

 

 

 

 

 

Frequency instructions

from

the

- Is the frequency setting mode selection parameter set to “computer”?

Section 8.1

computer have no effect.

 

 

 

 

Commands, including the run and

- Is the command mode selection parameter set to “computer”?

Section 8.1

stop commands, from the com-

 

 

 

muter have no effect.

 

 

 

 

 

During RS485

communication,

- Is the inverter connected correctly?

Refer

to

an inverter sends back respons-

- Are you sure the receive line and the send line are not in contact with

Appendix

 

es repeatedly an infinite number

each other?

2.

 

of times.

 

 

 

 

 

 

A change to a parameter does

Some communication-related parameters do not take effect until the

Chapter 7

not take effect.

 

 

 

inverter is reset. To make them take effect, turn the inverter off tempo-

 

 

 

 

 

 

rarily, then turn it back on.

 

 

The setting of a parameter was

When using the TOSHIBA Inverter Protocol, use the W command to

Section 4.2

changed, but it returns to its

write data into the EEPROM. If you use the P command that writes data

 

 

original setting when the inverter

into the RAM only, the data will be cleared when the inverters are reset.

 

 

is turned off.

 

 

 

 

 

 