efesotomasyon.com -Toshiba inverter,drive,servo,plc

E6581315

6. Inter-drive communication

Inter-drive communication (communication between inverters) are used, for example, when per- forming speed proportional control or load sharing torque control of two or more inverters without using a PLC or computer. The command is instructed by the operation from the master inverter’s panel or analog input, etc.

With the Inter-drive communication function, the master inverter continues to transmit the data se- lected by the parameters to all the slave inverters on the same network. The master inverter uses the S command for outputting instructions to the slave inverters, and the slave inverters do not re- turn the data. (See chapter 4.2 "Command".) Network construction for a simple synchronized op- eration and speed-proportional operation can be created by this function.

*If the master inverter trips, the slave inverters display the blinking error code “t” and come to a full stop (0Hz).

Restoring the master inverter that has tripped returns the slave inverters to working order.

*With the communication time-out parameters f803 and f804, you can specify what the slave inverters should do (continue to operate, issue an alarm or trip) if a cable is broken or the master inverter is turned off during operation.

*To use the inter-drive communication function, select “TOSHIBA Inverter Protocol” (, =) in the communication protocol selection parameters. “TOSHIBA Inverter Protocol” (, =) is set for communication protocol selection in Shipment setting. (See “3. Communication protocol.”)

<Conceptual illustration>

 

 

 

Master (60Hz)

Slave 1 (50Hz)

Slave 2 (40Hz)

Slave 3 (30Hz)

 

 

 

VF-AS1

VF-AS1

VF-AS1

VF-AS1

Analog input

<Notes>

Speed command can be transmitted but the run / stop signal is not issued. Slave station should have an indi- vidual stop signal or the function to stop the action by the frequency reference. (Setting is necessary for : Operation start frequency, : Operation start frequency hysteresis .)

For continuing the operation by the last received command value in the case of a communication breakdown, communications time-out time () to trip the slave inverters. The master inverter does not trip even though the communication breakdown happens. To trip the master inverter, provide an interlock mechanism by installing an FL fault relay point or the like from the slave side.

33

Page 34
Image 34
Toshiba TOSVERT VF-AS1 instruction manual Inter-drive communication