7. Communication parameters

The settings of communication-related parameters can be changed from the operation panel and

the external controller (computer). Note that there are two types of parameters: parameters whose

settings take effect immediately after the setting and parameters whose settings do not take effect

until the inverter is turned back on or reset.

Com-
munica-
tion
Number.
Title Function Adjustment range Unit Default
setting Valid Reference
0800  Baud rate
(2-wire RS485)
0: 9600bps
1: 19200bps
2: 38400bps
- 1 After reset. Section 7.1
0801  Parity (common)
0: Non parity
1: Even parity
2: Odd parity
- 1 After reset. Section 7.1
0802  Inverter number
(common) 0-247 1 0 Real time Section 7.2
0803 
Communication
time-out time
(common)
0:OFF
1-100s 1s 0 Real time Section 7.3
2-wire 4-wire
0- -
1 t alarm -
2Err5 trip -
3 - t alarm
4 t alarm t alarm
5 Err5 trip t alarm
6- Err5 trip
7 t alarm Err5 trip
0804 
Communication
time-out action
(common)
8 Err5 trip Err5 trip
1 8 Real time Section 7.3
0805  Send waiting time
(2-wire RS485)
0.00: Default
0.01-2.00s 0.01s 0. 00 Real time Section 7.4
0806 
Inverter-to-inverter
communication (2-
wire RS485)
0:Slave (issues a 0Hz command if some-
thing goes wrong with the master)
1:Slave (continues operation if something
goes wrong with the master)
2:Slave (trips for emergency stop if
something goes wrong with the master)
3:Master (sends a frequency command)
4:Master (sends an output frequency)
5.Master (sends a torque command)
6.Master (sends an output torque com-
mand)
- 0 After reset. Chapter 6
0807  Protocol selection
(2-wire RS485)
0: TOSHIBA
1:MODBUS-RTU - 0 After reset. Chapter 3
0810  Frequency point
selection
0:Disabled
1:2-wire RS485
2:4-wire RS485
3:Communication add option
- 0 Real time Sec tion 6.1
0811  Point 1 setting 0-100% - 0 Real time
0812  Point 1 frequency 0-Hz 0.01Hz 0.0 Real time
0813  Point 2 setting 0-100% - 100 Real time
0814  Point 2 frequency 0-Hz 0.01Hz 60.0 Real ti me
Section 6.1
0820 
Communication
speed
(4-wire RS485)
0: 9600bps
1: 19200bps
2: 38400bps
- 1 After reset. Section 7.1
0825  Send waiting time
(4-wire RS485)
0.00: Normal
0.01-2.00s 0.01s 0. 00 Real time Section 7.4