E6581315
5.1.2. Write command (06)
Computer → Inverter *The text size is 8 bytes fixed.
| 
 | 
 | Inverter | 
 | Commu- | Commu- | Write Data | Write Data | CRC | CRC | 
 | 
| 
 | (3.5bytes | Command | nication | nication | (3.5bytes | |||||
| 
 | Blank) | No. | 
 | No. (high) | No. (low) | (high) | (low) | (low) | (high) | Blank) | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||||
| 
 | 
 | 
 | 06 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1) Inverter No. (1 byte) | : Specify an inverter number between 0 and 247 (00H to F7H). | 
 | 
 | |||||||
| 
 | 
 | 
 | Command processing will be executed only broadcast communication “0” and with | |||||||
| 
 | 
 | 
 | those inverters that match set inverter numbers. | Data will not be returned if “0” | ||||||
(broadcast communication) and inverter numbers do not match.
| 2) | Command (1 byte) | : Set the write command (06H fixed). | 
 | 
 | 
 | 
 | 
 | 
 | |||||||
| 3) | Communication No. (2 bytes) : Set in the order of high to low numbers. | 
 | 
 | 
 | 
 | 
 | 
 | ||||||||
| 4) | Write data (2 bytes) | : Set in the order of high to low write data. | 
 | 
 | 
 | 
 | 
 | 
 | |||||||
| 5) | CRC (2 bytes) | 
 | : Set generation results of CRC in the order of low to high numbers. | For the method to | 
 | ||||||||||
| 
 | 
 | 
 | 
 | generate CRC, see “5.2 CRC Generation.” Note that the setting sequence is rever- | 
 | ||||||||||
| 
 | 
 | 
 | 
 | sal to that of others. | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |||
|  Inverter → Computer (Normal return) | *The text size is 8 bytes fixed. | 
 | 
 | 
 | 
 | 
 | 
 | ||||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | Inverter | 
 | 
 | Commu- | Commu- | Write Data | Write Data | CRC | 
 | CRC | 
 | 
 | |
| 
 | 
 | (3.5bytes | Command | 
 | nication | nication | 
 | (3.5bytes | 
 | ||||||
| 
 | 
 | Blank) | No. | 
 | 
 | No. (high) | No. (low) | (high) | 
 | (low) | (low) | 
 | (high) | Blank) | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||||
| 
 | 
 | 
 | 
 | 06 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1) | Command (1 byte) | : Write command (06H fixed) will be returned. | 
 | 
 | 
 | 
 | 
 | 
 | |||||||
| 2) | Write data (2 bytes) | : Returned in the order of write data (high) and (low). | 
 | 
 | 
 | 
 | 
 | ||||||||
 Inverter → Computer (Abnormal return) *The text size is 5 bytes fixed.
(3.5bytes
Blank)
| Inverter No. | Command | Error Code | CRC | CRC | |
| (low) | (high) | ||||
| 
 | 
 | 
 | |||
| 
 | 86 | 
 | 
 | 
 | 
(3.5bytes
Blank)
| 1) | Command (1 byte) | : 86H fixed (Read command error) (Command + 80H) | 
| 2) | Error code (1 byte) | : See “4.3 Transmission errors.” | 
Example: Writing in frequency command value (FA01) (60Hz)
| (Computer → inverter) | 01 06 FA 01 17 70 E6 C6 | 
| (Inverter → computer) | 01 06 FA 01 17 70 E6 C6 | 
Example: Communication number error
| (Computer → inverter) | 01 06 FF FF 00 00 89 EE | 
| (Inverter → computer) | 01 86 02 C3 A1 | 
Note
▼The EEPROM life is 10,000 operations.
Do not write in the same parameter that has an EEPROM more than 10,000 times.
31