E6581315

5.1.2. Write command (06)

„Computer → Inverter *The text size is 8 bytes fixed.

 

 

Inverter

 

Commu-

Commu-

Write Data

Write Data

CRC

CRC

 

 

(3.5bytes

Command

nication

nication

(3.5bytes

 

Blank)

No.

 

No. (high)

No. (low)

(high)

(low)

(low)

(high)

Blank)

 

 

 

 

 

 

 

 

 

 

06

 

 

 

 

 

 

 

1) Inverter No. (1 byte)

: Specify an inverter number between 0 and 247 (00H to F7H).

 

 

 

 

 

Command processing will be executed only broadcast communication “0” and with

 

 

 

those inverters that match set inverter numbers.

Data will not be returned if “0”

(broadcast communication) and inverter numbers do not match.

2)

Command (1 byte)

: Set the write command (06H fixed).

 

 

 

 

 

 

3)

Communication No. (2 bytes) : Set in the order of high to low numbers.

 

 

 

 

 

 

4)

Write data (2 bytes)

: Set in the order of high to low write data.

 

 

 

 

 

 

5)

CRC (2 bytes)

 

: Set generation results of CRC in the order of low to high numbers.

For the method to

 

 

 

 

 

generate CRC, see “5.2 CRC Generation.” Note that the setting sequence is rever-

 

 

 

 

 

sal to that of others.

 

 

 

 

 

 

 

 

„ Inverter → Computer (Normal return)

*The text size is 8 bytes fixed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter

 

 

Commu-

Commu-

Write Data

Write Data

CRC

 

CRC

 

 

 

 

(3.5bytes

Command

 

nication

nication

 

(3.5bytes

 

 

 

Blank)

No.

 

 

No. (high)

No. (low)

(high)

 

(low)

(low)

 

(high)

Blank)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

 

 

 

 

 

 

 

 

 

 

 

1)

Command (1 byte)

: Write command (06H fixed) will be returned.

 

 

 

 

 

 

2)

Write data (2 bytes)

: Returned in the order of write data (high) and (low).

 

 

 

 

 

„ Inverter → Computer (Abnormal return) *The text size is 5 bytes fixed.

(3.5bytes

Blank)

Inverter No.

Command

Error Code

CRC

CRC

(low)

(high)

 

 

 

 

86

 

 

 

(3.5bytes

Blank)

1)

Command (1 byte)

: 86H fixed (Read command error) (Command + 80H)

2)

Error code (1 byte)

: See “4.3 Transmission errors.”

„Example: Writing in frequency command value (FA01) (60Hz)

(Computer → inverter)

01 06 FA 01 17 70 E6 C6

(Inverter → computer)

01 06 FA 01 17 70 E6 C6

„Example: Communication number error

(Computer → inverter)

01 06 FF FF 00 00 89 EE

(Inverter → computer)

01 86 02 C3 A1

Note

The EEPROM life is 10,000 operations.

Do not write in the same parameter that has an EEPROM more than 10,000 times.

31

Page 32
Image 32