7.3.Communication time-out time (), Communication time-out action (f804)

The timer function is mainly used to detect a break in a cable during communication, and if no data is sent to an inverter within the preset time, this function makes the inverter trip () or issue an alarm (). With the communication time-out action parameter (), you can specify what the inverter should do (trip, issue an alarm or do nothing) if a time-out occurs.

„How to set the timer

By default, the communication time-out time parameter () is set to  (OFF).

*Timer adjustment range

About 1 sec. (01H) to about 100 sec. (64H) / Timer off (0H)

„How to specify what an inverter should do if a time-out occurs

By default, the communication time-out action parameter () is set to  ( trip) for both 2-wire and 4-wire RS485 communication.

*Selection of time-out action (Range: 0 to 8 ... For details refer to “6. Communication parameters.) The action of the inverter at the occurrence of a time-out can be selected from among “do noth- ing,” “trip ()” and “alarm ()” individually for two-wire and four-wire RS485 communica- tion.

„How to start the timer

If the timer is set from the operation panel, it will start automatically the instant when communication is established for the first time after the setting.

If the timer is set from the computer, it will start automatically the instant when communication is established after the setting.

If the timer setting is stored in the EEPROM, the timer will start when communication is established for the first time after the power has been turned on.

Note that, if the inverter number does not match or if a format error occurs, preventing the inverter from returning data, the timer function will assume that no communication has taken place and will not start.

„How to disable the timer

To disable the timer, set its parameter to 0.

Ex.: To disable the timer function from the computer (To store the timer setting in the EEPROM)

Computer Inverter

Inverter Computer

(W08030)CR

(W08030000)CR

... Sets the timer parameter to 0 to disable it.

„Timer

Time-out period

Computer link

Inter-drive communication

PC INV

Master INV

to Slave

INV

INV PC

PC INV

Master INV

to Slave

INV

The timer measures the time elapsed before the inverter ac- knowledges receipt of data after it acknowledged receipt of the previ- ous data.

43

Page 44
Image 44
Toshiba TOSVERT VF-AS1 „ Timer Time-out period Computer link, Master INV To Slave, Inv Inv → Pc Pc → Inv