Frequency setting from the computer “Communication Number: FA01, FA05”
Setting range: 0 to maximum frequency (fh)
This frequency command is enabled only when the frequency command by communication is en- abled. To make frequency commands from the computer valid, set the frequency setting mode se- lection parameter (fmod) to RS485 communication (communication No. 0004: 5
However, enabled commands and frequencies are given the priority if “48 (49): Forced switching
from communication to local,” “56 (57): Forced continuous operation,” or “58 (59): Specified speed operation” is set by input terminal function selection (f11o to f118).
Once enabled, this frequency setting will be enabled till disable is set (0 setting), power is turned off or is reset, or factory default setting (typ) is selected.
Set a frequency by communication hexadecimal in Communication Number FA01, FA05. (1=0.01Hz (unit))
Example: Operation frequency 80Hz command by
Torque command setting from the computer
4-wire RS485 communication: FA32
This section explains how to set a torque command value for inverters. The torque command value set here takes effect if torque commands from the computer are valid when the inverters are in tor- que control mode (in cases where torque control is selected with the terminal board or with a com- munication command when ( is set to 4 or 8).
To make torque commands from the computer valid, set the torque command selection parameter (communication No. 0420) to 5
When setting a torque for torque commands from the computer, specify a torque in hexadecimal (unit: 1=0.01%,
Example: 50% torque command (PFA321388) 50%=50÷0.01=5000=1388H
47